Prestige and VisionPRO EIM Spec Sheet 2013
Table Of Contents
- Application
- Features
- Contents
- Specifications
- System Installation
- Installation Options
- Guidelines for Installing RedLINK Devices
- Installing Equipment Interface Module (if used)
- Wiring 24 Vac Common
- Selecting Discharge and Return Air Temperature Sensor Mounting Locations
- Selecting Return Air Temperature Sensor Mounting Location
- Installing Discharge and Return Air Temperature Sensors
- Selecting Thermostat Location
- Installing Wallplate
- Power Optional REDLINK™ Accessories
- Performing Initial Setup
- Linking Thermostat to Equipment Interface Module (if used)
- Linking RedLINK™ Accessories
- Completing Initial Setup
- Adding RedLINK Accessories to the Thermostat
- Locating the Connect Buttons on RedLINK Accessories
- Finding Your Password (Date Code) to Access Installer Options
- Installer Options
- Making Changes to Installer Setup
- Installer Tests
- Operation
- Setting the time/date
- Setting the fan
- Setting system mode
- Preset Energy-Saving Schedules
- Adjusting program schedules
- Overriding schedules: residential use
- Overriding schedules: commercial use
- Viewing equipment status
- Setting vacation hold: residential use
- Setting holiday/event schedules: commercial use
- Setting custom events: commercial use
- Setting holiday schedule: commercial use
- Setting holiday override: commercial use
- Initiating occupancy mode: commercial use
- Remote setback: commercial use
- Adjusting humidification settings
- Adjusting dehumidification settings: residential use
- Adjusting dehumidification settings: commercial use
- Adjusting ventilation settings
- Customizing screen color
- Setting preferences
- Cleaning the thermostat screen
- Adjusting security settings
- Viewing dealer information
- Advanced Features
- Installer options
- Using the temperature display
- Using the humidity display
- Universal Outputs (U1, U2, U3)
- Universal Inputs (S1, S2, S3, S4)
- Alerts and Diagnostics
- Heat Pump and Backup Heat Operation
- Indoor Air Quality (IAQ) Control
- IAQ Reminders
- Customizable Reminders
- USB Port
- Commercial Features
- Overriding schedules: commercial use
- Setting holiday/event schedules: commercial use
- Setting custom events: commercial use
- Setting holiday schedule: commercial use
- Setting holiday override: commercial use
- Initiating occupancy mode: commercial use
- Ramp Rates
- Custom Names
- Remote Setback
- Economizer and Time of Day (TOD) Operation
- Pre-Occupancy Purge
- Battery Replacement
- Optional Accessories
- Portable Comfort Control
- Remote Indoor Sensors
- Backup Control
- Replacing a Thermostat
- Replacing an Equipment Interface Module
- Wiring
- EIM Wiring Diagrams
- THX9321 Thermostat Wiring Diagrams
- THX9321 Thermostat Wiring Diagrams Using Universal Relays to Control Heating or Cooling
- Wiring IAQ Equipment or a Heat/Cool Stage to the Universal Terminals
- Economizer Module Wiring Diagrams
- Wiring C7089U1006 Outdoor Sensor
- Wiring guide — Wired Indoor Sensors
- Zoning
- Troubleshooting
- Regulatory Information
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ WITH EIM
68-0311—02 134
BACKUP CONTROL
This section explains when backup control is used. For
example, if batteries in the wireless indoor sensors are
depleted.
If the Thermostat is Part of the Temperature
Average
1. The thermostat controls the system using the remaining
sensors that are part of the temperature average.
2. If there are no remote indoor sensors remaining, the
thermostat controls the system using its internal sensor.
3. If the internal thermostat sensor is not available and a
Return Air Sensor is connected, the Backup Control in
the EIM is used. The backup control maintains 55 °F in
heat, 85 °F in cool and operates the fan continuously to
sense and control temperature.
If the Thermostat is NOT Part of the
Temperature Average
1. The thermostat controls the system using the remaining
sensors that are part of the temperature average.
2. If there are no remote indoor sensors remaining and a
Return Air Sensor is connected, the Backup Control in
the EIM is used. The backup control maintains 55 °F in
heat, 85 °F in cool and operates the fan continuously to
sense and control temperature.
REPLACING A THERMOSTAT
When you replace a thermostat, you must reset the RedLINK
accessories before connecting them to the new thermostat.
Follow the instructions below:
At the Equipment Interface Module (EIM)
1. Press and hold the CONNECT button on the EIM until
the CONNECTED LED glows amber (hold for about 10
seconds).
2. Follow the prompts on the screen to connect the new
thermostat to the EIM. See page 10.
At the Portable Comfort Control
1. Press and hold the blank space (or arrow) in the lower
right hand corner of the screen until the display changes
(hold for about 4 seconds).
Fig. 316.
2. Press REMOVE, then YES to disconnect from the old
thermostats.
3. To reconnect the thermostat, go to “Linking RedLINK™
Accessories” beginning on page 16.
At the Indoor Sensor, RedLINK Internet
Gateway, Entry/Exit Remote, Vent-Filter
Boost Remote or TrueSTEAM Wireless
Adapter
1. Press and hold the CONNECT button on the accessory
until the status light glows amber (hold for about 10 sec-
onds).
2. To reconnect the thermostat, go to “Linking RedLINK™
Accessories” beginning on page 16.
REPLACING AN EQUIPMENT
INTERFACE MODULE
When you replace an EIM, you must reset the RedLINK
accessories before connecting them to the new thermostat.
Follow the instructions below:
At the thermostat
1. Press MENU, scroll down and select Installer Options,
enter the password (Date Code) when prompted, scroll
down and select Wireless Manager, scroll down and
select Remove Device, then select This Thermostat.
2. Follow the prompts on the screen to connect the thermo-
stat to the new EIM.
At the Portable Comfort Control
1. Press and hold the blank space (or arrow) in the lower
right hand corner of the screen until the display changes
(hold for about 4 seconds). See Fig. 316.
2. Press REMOVE, then YES to disconnect from the old
thermostats. To reconnect the thermostat, go to “Linking
RedLINK™ Accessories” beginning on page 16.
At the Indoor Sensor, RedLINK Internet
Gateway, Entry/Exit Remote, Vent-Filter
Boost Remote or TrueSTEAM Wireless
Adapter
1. Press and hold the CONNECT button on the accessory
until the status light glows amber (hold for about 10 sec-
onds).
2. To reconnect the thermostat, go to “Linking RedLINK™
Accessories” beginning on page 16.
Press and hold
the blank space
(or arrow may be
present)