VisionPRO Product Manual

VISIONPRO
®
8000 WITH REDLINK™
55 68-0312—02
1014 Vent During Hum
or Dehum Calls
Yes
No
Yes Both No This feature is used to help reach the user's
desired humidity level by not allowing the
ventilation equipment to run during a call for
humidification or dehumidification.
Yes: Ventilation is allowed to run during a call
for humidification or dehumidification.
No: Ventilation is NOT allowed to run during a
call for humidification or dehumidification.
1016 Vent On High
Indoor Humidity
Off
On
On Both No This ISU is only displayed when ISU 1000
Ventilation Type is set to ERV / HRV.
Off: The humidity level has no effect on
ventilation.
On: The thermostat removes excess humidity
by turning on the ventilator when the indoor
humidity rises 10% above the user's
humidification setting. The thermostat must
be in the heat mode to ventilate on high
humidity.
1017 Ventilator Core
Reminder
Off
3, 6, 9, 12 Calendar Months
Off Both No Ventilator Core Cleaning Reminder
1017 Ventilator Filter
Reminder
Off
3, 6, 9, 12 Calendar Months
Off Both No Ventilator Filter Cleaning Reminder
1100 Number of UV
Devices
0, 1, 2
0 Both No Press the up/down arrows to select the
number of UV devices installed in the system.
Some systems may have two UV devices, one
for the A-Coil and another for Air Treatment. A
replacement reminder can be setup for each
one. Select 0 if no UV devices are installed.
1105 UV Bulb 1
Reminder
Note: “1” is not
displayed if there
is only 1 UV Bulb
Off, 6, 12, 24 Calendar Months
Off Both No UV Bulb 1 Replacement Reminder
1105 UV Bulb 2
Reminder
Off, 6, 12, 24 Calendar Months
Off Both No UV Bulb 2 Replacement Reminder
1200 Custom
Reminders
View / Edit Custom Reminders
Add Custom Reminders
None Both No See “Customizable Reminders” beginning on
page 96.
28 Backlighting
On Demand
Continuous
On Demand Both No Select Continuous or On Demand
backlighting. Select Continuous backlighting if
you would like the backlight to be on all the
time (C wire is required for Continuous
backlighting).
Select On Demand backlighting if you would
like the backlight to only turn on after a key
press. After you complete your changes, the
screen stays lit for 16 seconds if the
thermostat is battery powered only or it stays
lit for 45 seconds if the thermostat is system
powered (C wire).
1400 Clock Format
12 hour
24 hour
12 Both No
1401 Daylight Saving
Time
Off
On
On Both No Set to Off in areas that do not follow Daylight
Saving Time.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes