VisionPRO Product Manual

VISIONPRO
®
8000 WITH REDLINK™
53 68-0312—02
1002 Ventilation Wiring
None
U1
U2
U3
Thermostat
defaults to the
next unused
universal
terminal (U1,
U2, U3).
Both No Number of Universal Outputs:
TH8321 Thermostat: U1 terminals
Equipment Interface Module (EIM): U1, U2
and U3 terminals
U1, U2, U3 are dry contacts that require
power. See “Wiring IAQ Equipment or a Heat/
Cool Stage to the Universal Terminals”
beginning on page 129.
1005 Ventilation
Method
ASHRAE
Percent On Time
Defaults to
ASHRAE
when ISU 101
Application is
set to
Residential.
Percent on
Time is the
only choice
when ISU 101
Application is
set to
Commercial.
Both No See “Ventilation Control Methods (ISU 1005)”
beginning on page 91.
1006 Vent Fan Control
Tstat Controls Fan
Equip Controls Fan
Tstat Controls
Fan
Both No Tstat Controls Fan: The thermostat turns on
the ventilation equipment and the fan when
ventilation is needed.
Equip Controls Fan: The thermostat turns on
the ventilation equipment when ventilation is
needed. The fan is controlled by the
equipment.
1009 Number of
Bedrooms
1 to 6
2 bedrooms Residential No This ISU is only displayed when ISU 1005
Ventilation Method is set to ASHRAE
(Residential only).
1009 Size of House
1000 to 5000 sq. ft. (in 100 sq. ft.
increments)
(90 to 460 sq. m.)
1000 sq. feet Residential No This ISU is only displayed when ISU 1005
Ventilation Method is set to ASHRAE
(Residential only).
1010 Ventilation Rate
30 to 350 CFM (in 5 CFM
increments)
(850 - 9900 LPM)
150 Residential No This ISU is only displayed when ISU 1005
Ventilation Method is set to ASHRAE
(Residential only).
1012 Vent Percent On
Time
10% to 100% (in 10%
increments)
30% Both No The thermostat operates ventilation
equipment based on a percentage entered in
the installer setup (ISU 1012). For example, if
Percent on Time is set to 50%, the ventilation
equipment will run at random times during a 1
hour period until it reaches a 50% run time
(approximately 30 minutes).
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes