VisionPRO Product Manual
VISIONPRO
®
8000 WITH REDLINK™
68-0312—02 48
711 Air Filter 1
Reminder
Note: “1” is not
displayed if there
is only 1 filter.
Off
Run Time:
10, 20, 30, 45, 60, 90, 120, 150
days
Calendar:
30, 45, 60, 75 days
3, 4, 5, 6, 9, 12, 15 months
Off Both No
711 Air Filter 2
Reminder
Off
Run Time:
10, 20, 30, 45, 60, 90, 120, 150
days
Calendar:
30, 45, 60, 75 days
3, 4, 5, 6, 9, 12, 15 months
Off Both No
712 EAC Cell
Reminder
Off
Calendar Months:
6, 7, 8, 9, 10, 11, 12 months
Off Both No Electronic Air Cleaner Cell Cleaning Reminder
712 EAC Pre-Filter
Reminder
Off
Calendar Months:
3, 4, 5, 6 months
Off Both No Electronic Air Cleaner Pre-Filter Cleaning
Reminder
712 EAC Post Filter
Reminder
Off
Calendar Months:
6, 7, 8, 9, 10, 11, 12 months
Off Both No Electronic Air Cleaner Post-Filter Replacement
Reminder
800 Humidifier Type
None
Steam
Bypass / Fan Pwrd
None Both No
801 Sensor for Hum
T-Stat Sensor
Remote Indoor Sensor Name
Remote Indoor Sensor Name
Remote Indoor Sensor Name
Remote Indoor Sensor Name
Remote Indoor Sensor Name
Remote Indoor Sensor Name
(Up to 6 Remote Indoor Sensors)
T-Stat Sensor Both No Select a sensor to control humidification
(thermostat or an optional remote sensor). If
multiple sensors are installed, you can use a
different sensor for dehumidification control.
See “Humidification control” beginning on
page 112.
Note: Humidity sensing cannot be averaged.
803 Humidifier Wiring
None
U1
U2
U3
Thermostat
defaults to the
next unused
universal
terminal (U1,
U2, U3).
Both No Number of Universal Outputs:
TH8321 Thermostat: U1 terminals
Equipment Interface Module (EIM): U1, U2
and U3 terminals
U1, U2, U3 are dry contacts that require
power. See “Wiring IAQ Equipment or a Heat/
Cool Stage to the Universal Terminals”
beginning on page 129.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes