VisionPRO Product Manual
VISIONPRO
®
8000 WITH REDLINK™
43 68-0312—02
510 Discharge Sensor
Type
10K
20K
10K Both No Select 10K or 20K based on the sensor
installed. Refer to resistance values below:
50062329-001 = 10K ohm
32005180-002 = 10K ohm
C7735A1000 = 10K ohm
C7770A = 20K ohm
C7041 = 20K ohm
511 A-Coil Low Temp.
Cutoff
Off
35° F to 65° F (in 5° F increments)
Off Both No If an optional Discharge Sensor is used, this
feature can help prevent icing on the air
conditioning A-Coil.
When temperature reaches the limit you set,
compressor(s) will shutoff while the system
fan continues to run, until the temperature
rises to a safe level.
600 Dry Contact
Device on S
Terminals
No
Yes
No Both Yes Dry Contact Alerts and Remote Setback
require an Equipment Interface Module. This
ISU is only displayed if an S1-S4 terminal is
available.
See “Dry Contact Alerts” beginning on
page 74 and “Remote Setback (Commercial
Use)” beginning on page 105.
600 Remote Setback
Dry Contact
No
Yes
No Commercial Yes Remote Setback requires an Equipment
Interface Module. This ISU is only displayed if
an S1-S4 terminal is available.
600 Full Drain Pan Dry
Contact Alert
No
Yes
No Both Yes Dry Contact Alerts require an Equipment
Interface Module. This ISU is only displayed if
an S1-S4 terminal is available.
See “Dry Contact Alerts” beginning on
page 74.
600 Dirty Filter Dry
Contact Alert
No
Yes
No Both Yes Dry Contact Alerts require an Equipment
Interface Module. This ISU is only displayed if
an S1-S4 terminal is available.
See “Dry Contact Alerts” beginning on
page 74.
600 Water Leak Dry
Contact Alert
No
Yes
No Both Yes Dry Contact Alerts require an Equipment
Interface Module. This ISU is only displayed if
an S1-S4 terminal is available.
See “Dry Contact Alerts” beginning on
page 74.
600 Sys. Shutdown
Dry Contact Alert
No
Yes
No Both Yes Dry Contact Alerts require an Equipment
Interface Module. This ISU is only displayed if
an S1-S4 terminal is available.
See “Dry Contact Alerts” beginning on
page 74.
600 Service Needed
Dry Contact Alert
No
Yes
No Both Yes Dry Contact Alerts require an Equipment
Interface Module. This ISU is only displayed if
an S1-S4 terminal is available.
See “Dry Contact Alerts” beginning on
page 74.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes