VisionPRO Product Manual
VISIONPRO
®
8000 WITH REDLINK™
41 68-0312—02
413 Residential:
Entry / Exit
Remote - Away
Heat Setpoint
Commercial:
Entry / Exit
Remote -
Unoccupied Heat
Setpoint
None
40° F to 90° F
Note: setpoint is limited based on
setting at ISU 410.
65° F Both No The thermostat maintains this Heat setting
when the user presses Away / Unoccupied at
the Entry / Exit Remote. Select None to delete
this temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See
“Wireless Entry/Exit Remote” beginning on
page 110.
414 Residential:
Entry / Exit
Remote - Vacation
Cool Setpoint
Commercial:
Entry / Exit
Remote - Holiday
Cool Setpoint
None
50° F to 99° F
Note: setpoint is limited based on
setting at ISU 410.
82° F Both No The thermostat maintains this Cool setting
when the user presses Vacation / Holiday at
the Entry / Exit Remote. Select None to delete
this temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See
“Wireless Entry/Exit Remote” beginning on
page 110.
414 Residential:
Entry / Exit
Remote - Vacation
Heat Setpoint
Commercial:
Entry / Exit
Remote - Holiday
Heat Setpoint
None
40° F to 90° F
Note: setpoint is limited based on
setting at ISU 410.
60° F Both No The thermostat maintains this Heat setting
when the user presses Vacation / Holiday at
the Entry / Exit Remote. Select None to delete
this temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See
“Wireless Entry/Exit Remote” beginning on
page 110.
500 Wired Sensor on
S Terminals
No
Yes
No Both No This ISU is only displayed if an S1–S4
terminal is available.
500 Wired Remote
Indoor Sensor
No
Yes
No Both No The thermostat will not display the Wired
Remote Indoor Sensor option if 6 wireless
indoor air sensors are already connected to
the thermostat. If you have a wired Indoor Air
Temperature network (1, 4, 9 etc), the
thermostat will allow up to 5 wireless indoor
air sensors.
500 Wired Outdoor
Sensor
No
Yes
No Both No The thermostat will not display the Wired
Outdoor Sensor option if a wireless outdoor
air sensor is already connected to the
thermostat.
500 Wired Return
Sensor
No
Yes
No Both Yes The thermostat will not display the Wired
Return Sensor option if there is no fan in the
system.
500 Wired Discharge
Sensor
No
Yes
No Both No The thermostat will not display the Wired
Discharge Sensor option if there is no fan in
the system.
501 Indoor Sensor
Name
[Select Indoor Sensor Name]
Indoor Sensor Both No Select a name (location) of the Wired Remote
Indoor Sensor.
502 Indoor Sensor
None
S1
S2
S3
S4
None Both No Select the terminals wired to the Remote
Indoor Sensor.
Number of Sensor Inputs:
Thermostat = S1
Equipment Interface Module = S1, S2, S3 and
S4
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes