VisionPRO Product Manual
VISIONPRO
®
8000 WITH REDLINK™
37 68-0312—02
406 Max. Heat
Recovery Ramp
Rate
Off
1° F/hr to 20° F/hr
8° F/hr Commercial No Off: The heating system will begin recovery at
the time that is scheduled.
When a Maximum Recovery Ramp Rate is
set, the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a Maximum Recovery Ramp Rate based
on the rate that the heating system can
recover at for a mild day in your region.
Default setting is 8° F / hour.
Set an Outdoor Temperature that is
representative of a mild day in your region to
be associated with the Maximum Recovery
Ramp Rate. The thermostat will begin
recovery at the optimal time based on a
calculated ramp rate, allowing the system to
recover on time and save energy during
changing outdoor conditions.
During recovery, the setpoint changes at a
rate in degrees per hour depending on the
outdoor temperature.
406 Max. Heat
Recovery Outdoor
Temp
Off
-20° F to 100° F
40° F Commercial No Off: The heating system will begin recovery at
the time that is scheduled.
When a Maximum Recovery Ramp Rate is
set, the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a Maximum Recovery Ramp Rate based
on the rate that the heating system can
recover at for a mild day in your region.
Default setting is 8° F / hour.
Set an Outdoor Temperature that is
representative of a mild day in your region to
be associated with the Maximum Recovery
Ramp Rate. The thermostat will begin
recovery at the optimal time based on a
calculated ramp rate, allowing the system to
recover on time and save energy during
changing outdoor conditions.
During recovery, the setpoint changes at a
rate in degrees per hour depending on the
outdoor temperature.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes