VisionPRO Product Manual
VISIONPRO
®
8000 WITH REDLINK™
68-0312—02 36
405 Min. Heat
Recovery Ramp
Rate
Off
1° F/hr to 20° F/hr
5° F/hr Commercial No Off: The heating system will begin recovery at
the time that is scheduled.
When a Minimum Recovery Ramp Rate is
set, the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a Minimum Recovery Ramp Rate based
on the rate that the heating system can
recover at for a cold day in your region.
Default setting is 5° F / hour.
If an outdoor sensor is installed, set an
Outdoor Temperature that is representative of
a cold day in your region to be associated with
the Minimum Recovery Ramp Rate. The
thermostat will begin recovery at the optimal
time based on a calculated ramp rate, allowing
the system to recover on time and save
energy during changing outdoor conditions.
During recovery, the setpoint changes at a
rate in degrees per hour depending on the
outdoor temperature. If there is no outdoor
sensor, the Minimum Recovery Ramp Rate is
used.
405 Min. Heat
Recovery Outdoor
Temp
Off
-20° F to 100°F
0° F Commercial No Off: The heating system will begin recovery at
the time that is scheduled.
When a Minimum Recovery Ramp Rate is
set, the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a Minimum Recovery Ramp Rate based
on the rate that the heating system can
recover at for a cold day in your region.
Default setting is 5° F / hour.
If an outdoor sensor is installed, set an
Outdoor Temperature that is representative of
a cold day in your region to be associated with
the Minimum Recovery Ramp Rate. The
thermostat will begin recovery at the optimal
time based on a calculated ramp rate, allowing
the system to recover on time and save
energy during changing outdoor conditions.
During recovery, the setpoint changes at a
rate in degrees per hour depending on the
outdoor temperature. If there is no outdoor
sensor, the Minimum Recovery Ramp Rate is
used.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes