VisionPRO Product Manual
VISIONPRO
®
8000 WITH REDLINK™
35 68-0312—02
400 Scheduled
Periods
2 or 4 periods per day
4 periods per
day
Both No Residential:
4 Periods = Wake, Leave, Return, Sleep
2 Periods = Wake, Sleep
Commercial:
4 Periods = Occupied 1, Unoccupied 1,
Occupied 2, Unoccupied 2
2 Periods = Occupied 1, Unoccupied 1
401 Pre-Occupancy
Purge
Off
1 hour
2 hour
3 hour
Off Commercial No Runs the fan 1 to 3 hours before each
occupied period to provide a comfortable
workplace upon arrival.
402 Type of Override
Standard
Initiate Occupancy
Standard Commercial No Standard:
The system maintains temperatures
programmed for the occupied and unoccupied
time periods. Pressing OVERRIDE will allow
the user to make a temporary schedule
change.
Initiate Occupancy:
The system maintains temperature at an
energy saving level until the user touches the
message center area on the thermostat. Note:
The message center displays Press HERE to
Start Occupancy. The system will then
maintain a comfortable temperature until the
occupied period ends. This option is
recommended for cost savings when the
workplace is used infrequently or arrival times
change from day to day (example - schools).
After the user touches Press HERE to Start
Occupancy, the user will still be able to
perform a standard OVERRIDE of the
schedule.
403 Override Duration
No Limit
1 to 12 Hours
3 hours Commercial No When the user presses the OVERRIDE button,
the thermostat will maintain the new
temperature for at least 1 hour. The user can
adjust the Hold Until time from 1 hour to the
amount set for the Override Duration (1-12
hours). Default setting is 3 hours. If set to No
Limit, the user can adjust the Hold Until time
up to 24 hours.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes