VisionPRO Product Manual

VISIONPRO
®
8000 WITH REDLINK™
68-0312—02 32
314 Cool Cycles Per
Hour Stage 3
1 to 6 CPH
3 Commercial No This ISU is only displayed when ISU 101
Application is set to Commercial and ISU 207
Cool Stages is set to 3 stages.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system
cycles less often when load conditions are
less than or greater than a 50% load.
314 Cool Cycles Per
Hour Stage 4
1 to 6 CPH
3 Commercial Yes This ISU is only displayed when ISU 101
Application is set to Commercial and ISU 207
Cool Stages is set to 4 stages.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system
cycles less often when load conditions are
less than or greater than a 50% load.
315 Heat Cycles Per
Hour Stage 1
Note: Depending
on the application,
the text displayed
on the screen may
show the specific
heating equipment
type. “Stage 1" is
not displayed if
there is only 1
stage.
1 to 12 CPH
Conv. Forced
Air = 5 CPH
Heat Pump = 3
CPH
Radiant Heat =
3 CPH
Both No This ISU is only displayed when ISU 207 Heat
Stages is set to 1 stage.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system
cycles less often when load conditions are
less than or greater than a 50% load. The
recommended cycle rate settings are below
for each heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH
High Efficiency Gas Forced Air = 3 CPH
Oil Forced Air = 5 CPH
Electric Forced Air = 9 CPH
Hot Water Fan Coil = 3 CPH
Hot Water Radiant Heat = 3 CPH
Geothermal Radiant Heat = 3 CPH
Steam = 1 CPH
Gravity = 1 CPH
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes