VisionPRO Product Manual

VISIONPRO
®
8000 WITH REDLINK™
29 68-0312—02
306 Compressor Heat
Diff. Stage 1
Comfort
1.0° F to 4.0° F from setpoint (in
0.5° F increments)
Comfort Both No ISU 301 Control Options must be set to
Advanced to view or adjust this ISU.
This ISU is only displayed if ISU 201 Heating
Equipment is Geothermal Radiant and ISU
205 Geo Forced Air is set to Heating and
Cooling.
The indoor temperature must drop to the
selected differential setting before the
thermostat will turn on the stage of heating.
For example, if stage 1 is set to 2° F (1.0° C),
the indoor temperature must be 2° F (1.0° C)
away from the setpoint before stage 1 turns
on. When set to Comfort, the thermostat will
use the stage of heating as needed to keep the
indoor temperature within 1° F (0.5° C)
degree of the setpoint.
306 Compressor Heat
Diff. Stage 2
Comfort
1.0° F to 4.5° F from setpoint (in
0.5° F increments)
Comfort Both No ISU 301 Control Options must be set to
Advanced to view or adjust this ISU.
This ISU is only displayed if ISU 201 Heating
Equipment is Air to Air Heat Pump,
Geothermal or Geothermal Radiant and there
are 2 compressor stages.
The indoor temperature must drop to the
selected differential setting before the
thermostat will turn on the stage of heating.
For example, if stage 2 is set to 2° F (1.0° C),
the indoor temperature must be 2° F (1.0° C)
away from the setpoint before stage 2 turns
on. When set to Comfort, the thermostat will
use the stage of heating as needed to keep the
indoor temperature within 1° F (0.5° C)
degree of the setpoint.
308,
309
Backup Heat
Droop Stage 1
Note: “Stage 1" is
not displayed if
there is only 1
stage of Backup
Heat.
Comfort
2.0° F to 15.0° F from setpoint (in
0.5° F increments)
Comfort Both No A backup heat droop can be set on any system
that has more than one heating equipment
type.
See “Backup Heat Droop” beginning on
page 76.
The Comfort setting is NOT available for Dual
Fuel systems. For example, Heat Pumps with
Gas Forced Air.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes