Product Data and Specifications - Fresh Air Ventilation System

Y8150 FRESH AIR VENTILATION SYSTEM, W8150 FRESH AIR VENTILATION CONTROL
7 68-0282—09
Setting the control...
1. Be sure power is turned on.
2. Set the Ventilation Standard on the control.
3. Set the bedrooms dial.
4. Set the area (sq ft) dial.
5. Set the airflow (cfm) dial.
6. Press the test button and observe the lights:
Green light is flashing.
The dial settings meet the chosen standard.
Red light is flashing.
There is not enough fresh air delivered to meet the
requirements of the selected standard. See
Troubleshooting section.
7. Record settings on the label inside the cover as
shown in the diagram.
TIPS:
Ventilation control reads new dial setting only when test
button is pushed or power is cycled. To ensure dial
settings are read, push test button after any changes are
made.
For single bedroom homes, set the bedrooms dial to 2
(this may result in more ventilation than the minimum
required).
For homes having more than five bedrooms and only a
single ventilation system, set the bedrooms dial to 5
(this may result in less ventilation than the minimum
required).
For conditioned square feet, set area (sq ft) dial to the
nearest value.
For airflow, set airflow (cfm) dial to the nearest value.
Vaulted ceilings do not need to be considered when
setting this control.
For homes with multiple systems: Honeywell
recommends a ventilation control and fresh air intake
for each system. Measure ventilation airflow for each
system independently. Refer to Multi-system Setup
Example for further details.
Customizing the ventilation control.
Honeywell
Golden Valley, MN 55422
50001159-001 Rev. A
W
8150A
1001
1
www.honeywell.com/yourhome
or call 1-800-468-1502
_________
area (sq. ft.)
R
ec
o
r
d
se
tt
ing
s
a
bo
ve
Ventilation Limit*
Ventilation
Standard
1
2
60%
ASHRAE 62.2
100%
62-1999
Installer
Test
M19991
Para español ver las instrucciones
*See Instructions Voir mode d'emploi en français inclus
R
C
DMP
DMP
AUX
AUX
REM
REM
24 VAC
XFRM
HVAC
Stat
Damper
ERV/Fan
Timer/Switch
G
F
R
C
C
C
C
H
W
G
T
Patent Pending
_________
bedrooms
_________
airflow (cfm)
Date installed:________________________
W8150A 1001
_________
area (sq. ft.)
Record settings above
Ventilation Limit*
Ventilation
Standard
1
2
60%
ASHRAE 62.2
100%
62-1999
Installer
Test
R
C
DMP
DMP
AUX
AUX
REM
REM
24 VAC
XFRM
HVAC
Stat
Damper
ERV/Fan
Timer/Switch
G
F
R
C
C
C
C
H
W
G
T
_________
bedrooms
_________
airflow (cfm)
Date installed:________________________