Product Data and Specifications - Fresh Air Ventilation System
Table Of Contents
Y8150 FRESH AIR VENTILATION SYSTEM, W8150 FRESH AIR VENTILATION CONTROL
5 68-0282—09
Installing fresh air damper, ducting,
and control…
1. Disconnect power from HVAC system.
2. Install the weather hood, ducting, and damper follow-
ing local practices. Be sure all duct and insulation
seams are tightly sealed.
3. Mount the transformer and control.
TIPS:
• In general, larger ducting allows higher airflow,
minimizes additional fan run time and may be needed
for larger homes.
• Installing a damper directly to the return duct may be
convenient to support the damper and reduce ducting.
• Fresh air connection should be downstream of sensors
(such as a humidistat) in return air plenum.
• The EARD6TZ end stops can be used to reduce the
amount of airflow in the duct. To prevent complete
opening, move the red tab to the desired range stop
location.
Wiring the control…
CAUTION
Electrical Hazard.
Can cause personal injury or equipment damage.
Disconnect power to all systems before beginning
installation.
1. Wire the control. See wiring diagrams in Fig. 1-10 as
listed below. All wiring must comply with local codes,
ordinances, and regulations.
2. Reapply power to system and control.
TIP:
• Control package allows wire routing through side slots
and bottom openings.
M35187
RANGE STOP
LOCATIONS
System Hookup Diagrams Fig. No. Page No.
Single transformer, conventional 1 10
Dual transformer, conventional 2 10
Multi-stage, conventional 3 10
Heat pump without emergency
heat
410
Heat pump with emergency heat 5 11
Accessory Hookup Diagrams Fig. No. Page No.
Wiring with a PC8900 Thermostat 6 11
Wiring with a remote switch/timer 7 11
Wiring to an HRV/ERV 8 11
Wiring an exhaust fan 9 11
Wiring a fan for a steam humidifier 10 12