Install Instructions
VC2, VC4, VC60, VC8
95C-10920—03 2
[1] with Snubber circuit
[2] Plenum rated with 5 meter cable
[3] Some models are not available in all countries. Not all VC
Actuator modes are shown.
Fig. 1. Nominal Dimensions in inches and millimeters
[1] No adapters
[2] Suitable for use as15 mm compression fitting
[3] Dimensions shown with nuts and olives installed
[4] Some models not available in all countries
MANUAL OPENER
The manual opener can be manipulated only when in the up
position. The “A” port can be opened by firmly pushing the
white manual lever down to midway and in. In this position
both the “A” and “B” ports are open, and with auxiliary switch
models the switch is closed. This "manual open" position may
be used for filling, venting, or draining the system, or for
opening the valve in case of power failure. The valve can be
restored manually to the closed position by depressing the
white manual lever lightly and then pulling the lever out. The
valve and actuator will return to the automatic position when
power is restored.
NOTE: If the valve is powered open (the lever is down), it
can not be manually closed unless actuator is
removed.
Table 1. Actuator Model Identifiers
Model No. Power
Control
Input
Auxiliary
Switch
Special
Features
INTERNATIONAL MODEL [3]
VC2010zz00 24V~50Hz SPDT
—
Molex™
VC2011zz00 24V~50Hz SPDT
—
Cable
VC2012zz00 [1] 24V~50Hz SPDT
—
Molex™
VC2611zz00 24V~50Hz SPDT Yes Cable
VC4012zz00 200-240V~ 50-60Hz SPST
—
Molex™
VC4013zz00 200-240V~ 50-60Hz SPST
—
Cable
VC4013zz11 200-240V~ 50-60Hz SPST
—
Cable
VC4613zz00 200-240V~ 50-60Hz SPST Yes Cable
VC6012zz00 200-240V~ 50-60Hz SPDT
—
Molex™
VC6013zz00 200-240V~ 50-60Hz SPDT
—
Cable
VC6013zz11 200-240V~ 50-60Hz SPDT
—
Cable
VC6612zz00 200-240V~ 50-60Hz SPDT Yes Molex™
VC6613zz00 200-240V~ 50-60Hz SPDT Yes Cable
VC8011zz00 24V~50Hz SPST
—
Cable
VC8611zz00 24V~50Hz SPST Yes Cable
NORTH AMERICA MODELS [3]
VC2114zz11 24V~60Hz SPDT
—
Plenum [2]
VC2714zz11 24V~60Hz SPDT Yes Plenum [2]
VC4011zz11 120V~60Hz SPST
—
Cable
VC4013zz11 200-240V~ 50-60Hz SPST
—
Cable
VC8111zz11 24V~60Hz SPST
—
Cable
VC8114zz11 24V~60Hz SPST
—
Plenum [2]
VC8711zz11 24V~60Hz SPST Yes Cable
VC8714zz11 24V~60Hz SPST Yes Plenum [2]
Table 2. VC Valve assembled dimensions
Dimension C D E
[4]
Pipe
Fitting Sizes mm inches mm inches mm inches
1/2” BSPP (int.) [2] 98 3-7/8 111 4-3/8 136 5-11/32
1/2” BSPT (int.)
3/4” BSPP (int.) 94 3-11/16 113 4-7/16 130 5-1/8
3/4” BSPT (int.)
3/4” BSPP (ext.)
22mm Compression
[3]
112 4-7/16 140 5-1/2
1” BSPP (int.) 94 3-11/16 136 5-11/32
1” BSPP (ext.) 95 3-11/17 114 4-7/17 137 5-11/33
1” BSPT (int.) 94 3-11/16 113 4-7/16 136 5-11/16
28mm Compression
[3]
116 4/9/16 147 5-13/16
North America Standard Models
3/8” Flare [1] 98 3-7/8 111 4-3/8 136 5-11/32
1/2” Sweat 89 3-1/2 130 5-1/8
1/2” Flare [1] 98 3-7/8 136 5-11/32
1/2” Inverted Flare
[1]
1/2” NPT (int.)
3/4” NPT (int.) 94 3-11/16 113 4-7/16 130 5-1/8
3/4” Sweat 132 5-3/16
1” NPT (int.) 136
1” Sweat 5-11/32
1-1/4” Sweat 110 4-5/16 118 4-5/8 142 5-5/8
1-1/4” NPT (int.)