Manual
V5013N THREE-WAY THREADED GLOBE VALVE
63-2549—3 B.B. Rev. 11-03 www.honeywell.com
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
Automation and Control Solutions Honeywell International Honeywell Europe S.A. Honeywell Latin American
Honeywell International Inc. Honeywell Limited-Honeywell Limitée Control Products 3 Avenue du Bourget
Region
1985 Douglas Drive North 35 Dynamic Drive Honeywell Building 1140 Brussels 480 Sawgrass Corporate Parkway
Golden Valley, MN 55422 Scarborough, Ontario 17 Changi Business Park Central 1 Belgium Suite 200
M1V 4Z9 Singapore 486073 Sunrise FL 33325
CHECKOUT
Use the following procedure to check for proper valve
operation:
1. Check the valve body and connections for leaks.
IMPORTANT
Before installing linkage and actuator, make sure that
the valve stem operates freely. Impaired stem
operation can indicate that the body was twisted or
the stem was bent. Either of these conditions can
require valve replacement.
2. After installing linkage and actuator, check the operation
according to the installation information furnished with
these controls.
3. Operate the system through one complete cycle to
ensure the valve controls properly.
4. Check the valve at regular intervals for leakage around
the packing.
NOTE: The packing is spring-loaded and should
seldom require attention.
5. If leakage is discovered and inspection shows that the
packing gland is screwed down tightly, then repack the
valve.