Submittal Sheet
V5013B-F THREE-WAY MIXING & DIVERTING VALVES
9
77-5316-1
77-5316
Table 5. Electric Actuator and Linkage Selection.
Table 4. Pneumatic Actuator Selection.
Linkage (lbf)
Linkage
Model/Usage
Spring
Return
Torque
(lb-in.)
2-Position
Model†
Floating
Model†
Proportional
Model†
80 Q5001A Yes 25 M8175 — —
160 Q5001A for 3 in.
& smaller valves
Yes 60 M8185
M8186
M6285
M6286
M7285§
M7286§
No 75 — M6174 M7274§
No 150 — M6184 M7284§
160 Q5001B for 4, 5,
& 6 in. Valves
No 150 — M6184 M7284§
320 Q5001A for 3 in.
& smaller valves
No 300 — M6194 M7294§
Q5001B for 4, 5,
& 6 in. valves
80 Integral ——ML684 ML684 —
160 Integral ——ML684 ML684 ML784
Minimum Actuator Torque Required
for Linkage
Linkage
(lbf)
1/2 In. Through 3 In.
Valve Sizes (lb-in.)
4, 5, 6 In. Valve
Sizes
80 25 —
160 50 100
320 300 300
†Actuator shaft rotation must be 160 degrees
§2 to 10V dc
3/4 In. Stroke 1-1/2 In. Stroke
With Positioner
(Actuator Dia in In.)
Without Positioner
(Actuator Dia in In.)
With
Positioner
(Actuator Dia
in In.)
Without
Positioner
(Actuator Dia
in In.)
Valve Size in
DA
MP953E
RA
MP953F
Industrial
Type 01-15
DA
MP953C
RA
MP953D
DA
MP953E
DA
MP953C
Model Inches 5 8 13 7-1/8 or 01-18S 5 8 1 3 7-1/8 13 13
V5013B & D 2-1/2 — X X X — — X X X — —
(Mixing) 3 — X X X — — X X X — —
V5013C & E 4 — — — — — — — — — X X
(Diverting) 5 — — — — — — — — — X X
Three-Way 6 — — — — — — — — — X X
Flanged End 8 — — — — X — — — — — —
Connections
V5013F 1/2 X X — X — X X — X — —
Three-Way 3/4 X X — X — X X — X — —
Mixing with 1 X X — X — X X — X — —
Screwed End 1-1/4 X X — X — X X — X — —
Connections 1-1/2 X X — X — X X — X — —
2XX—X — XX— X — —