User Guide
TStatSpec
TM
43
GETTING CONNECTED TO THE DEVICE
Connecting to the device
This section describes the procedure of connecting to the
USB-TIM adapter. When you launch TStatSpec™, it
automatically detects the USB-TIM adapters connected to the
PC and establishes the connection to the first USB-TIM it
comes across.
If TStatSpec™ is already launched and then you connect the
USB-TIM adapter, press F2 or click on the ‘Connect to USB-
TIM’ icon in the toolbar to connect to the USB-TIM
adapter.You can also select ‘Connect’ option from USB-TIM
menu.
Click on the ‘Disconnect from USB-TIM’ icon in the toolbar or
press Ctrl+F2 to close connection between TStatSpec™ and
the USB-TIM.
Icons:
If the USB-TIM adapter is disconnected from the PC at any
point (after TStatSpec™ is established connection to USB-
TIM), the following warning message is displayed and any
subsequent online operations will fail. Re-connect the USB-
TIM adapter and press F2 or click on the ‘Connect to USB-
TIM’ icon in the toolbar.
NOTE:
1. Connection status indicates connection to USB-
TIM only, it does not indicate if T7350 is actually
connected.
2. Connect and Disconnect options are available
only if a Configuration is opened in the TStat-
Spec™.
3. When other USB devices other than USB-TIM are
connected to the PC, TStatSpec might not be able
to detect USB-TIM and hence cannot communi-
cate to T7350. Workaround: If TStatSpec is
unable to connect to the USB-TIM inspite of
proper connections, remove other Prolific devices
and connect only the USB-TIM device.
Indicates that the USB-TIM adapter is
disconnected. Click this button to
establish the connection between
USB-TIM adapter and TStatSpec™
tool.
Indicates that the USB-TIM adapter is
connected. Click this button to close
the connection between USB-TIM
adapter and TStatSpec™ tool.