User Guide

TStatSpec
TM
40
The Alarms screen will display the status of all system alarms and
associated errors in the T7350 controller.
The following list of system alarms will be shown in the Alarms
screen:
The first group Alarm –Sensor Fail" shows following errors associated
with alarm:
Local Space Sensor
Remote Space Sensor
Outdoor Sensor
Loc Humidity Sensor
Rem Humidity Sensor
Remote Setpt
Disch Air Sensor
The Second group Alarm – Invalid I/O Config shows the following
error associated with alarm:
Invalid I/O Config
The Third group Alarm – Invalid Subbase shows the following errors
associated with alarm:
Subbase/Cover Mismatch
Bad Subbase Type
Systems in alarm status will display the text ALARM next to them in
red color, while those that are not will display the text NORMAL in
green color.
The timer field on all monitor screens displays the current
times from the corresponding T7350 device that is being
monitored.
NOTE: If the time is not configured in Thermostat, the moni-
toring shows invalid time and date. After setting a
valid time and date in the thermostat, the monitoring
screens display a proper time.
T7350 Calibration
Description:
The T7350 Calibration screen allows the user to calibrate the
space temperature sensor. This option is available only for
online controllers.
Procedure:
1. Click Calibrate in the workspace or select Calibrate
from the Controller menu.
T7350CS calibration screen opens.
Fig. 38. Calibration Page
The following is a description for each of the fields.
MEASURED VALUE:
This is the actual value of space temperature read by the controller.
This is inclusive of any calibration offsets that a particular controller
applies to the actual value read.
EXPECTED VALUE:
Takes the user input value as the true value the sensor should be
detecting.
CALCULATED OFFSET:
Displays the difference between the actual and edit value.
CALIBRATE:
Enter the user input value for the temperature and click and Calibrate
button. The Space Temperature is calibrated to the value entered by
the user. The space temperature can be calibrated to a minimum of –
4 deg F( -2.2 deg C) and to a maximum of 3 deg F(1.7 deg C). If the
user enters out-of-range values, TStatSpec
warns about the above
limits and calibrates to the nearest valid offset value.
REFRESH:
Click on this button to refresh the temperature values.
CLOSE:
Closes the calibration screen.
HELP:
Click on this button to display help.
NOTE: When the space temperature is calibrated, it causes
a change in the configuration and the configuration
ID. It is a good idea to get the configuration ID again
from TStatSpec configuration screens and input
the it into the thermostat.
T7350 Diagnostics
Description:
After configuration and downloading, the controller is put into
diagnostic mode and checked for proper operation. This
operation forces the outputs to manual mode and checks their
operation. In this mode, the controller outputs are not driven
Button Description
Print Prints the current screen along with values to
the configured printer. (Opens the default
Windows print option screen)
Update Updates the existing values of all the fields of
current screen with latest values from device.
Apply Saves the current changes to device and as
well database
Exit Exit from the monitoring screen
Help Open the help screen (this document)