User Guide

TStatSpec
TM
22
a
Factory jumper between RC and RH for systems with one transformer.
b
The modulating subbase doesn't support heat pumps.
c
Can also be used for W2 or Y2.
Communicating Subbase
Communicating Subbases have one of the following configurations:
Three Heat /Three Cool:
This subbase allows for conventional or heat pump operation. A total of eight relays are available with thermostat cover assembly
and subbase. The auxiliary relay may be configured for an economizer, TOD, or dehumidification. This subbase may be
configured for 2 Heat / 4 Cool by using the third stage of heat for an additional stage of cooling.
4 additional relays. Stage 2 heating, Stage 3 heating (or Stage 4 cooling relay), Stage 2 cooling, and Stage 3 cooling.
Humidity sensor mounted in subbase.
Remote Room Sensor, T7770 or TR 21 or TR22 or TR23 or TR24 /T7771 Wall Module.
Remote Room Humidity Sensor.
Remote Discharge Air Temperature Sensor.
Remote Outdoor Air Temperature Sensor.
Remote Occupancy Input (Digital Input).
Access to the serial communications port on the thermostat.
Terminals for base wall plate are listed in the table given below.
T4 N/A Remote sensor input for T7770 or TR 21 or TR22 or TR23 or TR24 / T7771.
T5 N/A Remote setpoint input for T7770 or TR 21 or TR22 or TR23 or TR24 / T7771.
T6 N/A Remote bypass input for T7770 or TR 21 or TR22 or TR23 or TR24 / T7771.
T7 N/A Remote LED output for T7770 or TR 21 or TR22 or TR23 or TR24 / T7771.
Terminal
Conventional
Terminal Ht Pump Description
RC
a
RC
a
24 VAC Cooling transformer.
RH
a
RH
a
24 VAC Heating transformer.
X X Common.
G G Fan relay. (uses RC)
aux aux Auxiliary relay. (uses RH)
W1 O/B Conventional: Stage 1 heating relay.
Heat Pump: Changeover relay for heating (B) or cooling (O). (uses RH)
W2 W1 Conventional Stage 2 heating relay.
Heat Pump: 1
st
Stage auxiliary heat relay. (uses RH)
W3/Y4 W2 Conventional: Stage 3 heating or stage 4 cooling relay.
Heat Pump: 2
nd
Stage auxiliary heat relay. (uses RH)
Y1 Y1 Conventional Stage 1 cooling relay.
Heat Pump: Stage 1 compressor relay. (uses RC)
Y2 Y2 Conventional Stage 2 cooling.
Heat Pump: Stage 2 compressor relay. (uses RC)
Y3 -- Conventional Stage 3 cooling relay.
Heat Pump: Not Used (uses RC).
AS AS Discharge Air Sensor connection. (1)