Daim Ntawv Qhia Tus Neeg Siv

UDC2800 Universal Digital Controller Quick Start Guide
Step Operation Press Result
1 Enter Set Up Mode Setup key Enter in the first set up group, Security.
2 Select any Set Up group
Setup key or Increment
or Decrement keys
Sequentially displays the other set up groups shown in the prompt hierarchy.
See Configuration Record Sheet for prompts.
You can also use the Increment or Decrement keys to scan the set up groups
in both directions. Stop at the set up group tile that describes the group of
parameters you want to configure. Then proceed to the next step.
3
Select a Function
parameter
Function key Enter in the first function prompt of the selected set up group.
Increment or
Decrement keys
Press Increment or Decrement keys to display the other function prompts of
the selected set up group. Stop at the function prompt that you want to
change.
4
Change the Value or
Selection
Function key Enter in the value or selection of the selected function prompt.
Increment or
Decrement keys
Increment or decrement the value or selection that appears for the selected
function prompt.
You can press the Increment and Decrement keys at the same time to move the
current editable digit one step left.
5
Enter the Value or
Selection
Function key Enter value or selection made into memory.
6 Exit Configuration Lower Display key Exit the set up mode and returns to the main screen.
Configuration Procedure
Group
Prompt
Function Prompt Value or
Selection
Factory Setting Group
Prompt
Function Prompt Value or
Selection
Factory Setting
Algorithms Control Algorithm
Timer Function
Period Hrs:Mins
Start Trigger
Low Display
Reset Trigger
Increment
Input Algorithm 1
Math K
Calculated High
Calculated Low
Algorithm 1 Input A
Algorithm 1 Input B
Algorithm 1 Input C
Percent CO
Algorithm 1 Bias
Percent H2
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
PID A
Disable
0.01
Keyboard
Timer Remaining
Keyboard
Minutes
None
1.0
1000
0
Input 1
Input 2
None
0.200
0.000
1.000
Output Output Algorithms
Output Range
Relay State
Relay Type
Motor Time
Current Output
CO Low Value
CO High Value
CO Range
――――
――――
――――
――――
――――
――――
――――
――――
――――
Model No. dependent
100 Percent
1 Off 2 On
Electromechanical
30
Disable
0.0
100.0
4-20mA
Input1
Input 1 Type
Input 1 Transmitter
Input 1 High Value
Input 1 Low Value
Input 1 Ratio
Input 1 Bias
Input 1 Filter
Input 1 Burnout
――――
――――
――――
――――
――――
――――
――――
――――
0-10 mV
Linear
1000
0
1.00
0
1
No Burnout
Input2 Input 2 Type
Input 2 Transmitter
Input 2 High Value
Input 2 Low Value
Input 2 Ratio
Input 2 Bias
Input 2 Filter
Input 2 Burnout
――――
――――
――――
――――
――――
――――
――――
――――
0-10 mV
Linear
1000
0
1.00
0
1
No Burnout
Control
PV Source
PID Sets
Switchover Value 1/2
Switchover Value 2/3
Switchover Value 3/4
Local SP Source
Remote SP Source
Autobias
SP Tracking
Power Up Mode
TPSC Power Up Mode
SP High Limit
SP Low Limit
Action Direction
Output Rate
Rate Up % Min
Rate Down % Min
Output High Limit
Output Low Limit
Integral High Limit
Integral Low Limit
Dropoff
Deadband
Output Hysteresis
Failsafe Mode
Failsafe Value
SW Failsafe Value
Preset Manual Output
Preset Auto Output
Proportion Unit
Reset Unit
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
Input 1
1 Set
0.00
0.00
0.00
1 Local SP
None
Disable
None
Manual/Local SP
Failsafe
1000
0
Reverse
Disable
0
0
100
0
100
0
0
1.0
0.5
Non Latching
0
--
0
0
Gain
Minutes/Repeat
Alarms A1S1 Type
A1S1 Value
A1S1 State
A1S1 Event
A1S1 Delay
A1S1 Hysteresis
A1S2 Type
A1S2 Value
A1S2 State
A1S2 Event
A1S2 Delay
A1S2 Hysteresis
A2S1 Type
A2S1 Value
A2S1 State
A2S1 Event
A2S1 Delay
A2S1 Hysteresis
A2S2 Type
A2S2 Value
A2S2 State
A2S2 Event
A2S2 Delay
A2S2 Hysteresis
Alarm Output 1
Alarm Blocking
AO/CO Diagnostic
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
None
90
High Alarm
End of Segment
0
0.1
None
10
Low Alarm
Begin of Segment
0
0.1
None
95
High Alarm
End of Segment
0
0.1
None
5
Low Alarm
Begin of Segment
0
0.1
Non Latching
Disable
Disable
Options
Auxiliary Output
CO Range
CO Low Value
CO High Value
DI 1 Function
DI 1 Combination
DI 2 Function
DI 2 Combination
――――
――――
――――
――――
――――
――――
――――
――――
Disable
4-20 mA
0.0
100.0
None
Disable
None
Disable
Display Decimal Digits
Temperature Unit
Input 2 Ratio
Language
TC Diagnostics
Theme
――――
――――
――――
――――
――――
――――
None
None
Disable
English
Enable
Bright
Configuration Record Sheet
Enter the value or selection for each prompt on this sheet so you will have a record of how your controller was configured.
Group Prompt Function Prompt Value or
Selection
Factory
Setting
Group Prompt Function Prompt Value or
Selection
Factory
Setting
Security
Password
Lockout
Auto/Man Key
Run/Hold Key
SP Select Key
Restore Settings
Restore*
Change Password
――――
――――
――――
――――
――――
――――
――――
――――
0
Calibration
Enable
Enable
Enable
Disable
Disable
- -
Accutune
Fuzzy Suppression
Accutune
Duplex Output
Error Status
――――
――――
――――
Read only
Disable
Disable
Manual
None
Tuning
Proportional Band 1
or
Gain 1 or
Rate Min
Reset Mins/Rpt 1
or
Reset Rpts/Min 1
Manual Reset
Proportional Band 2
or
Gain 2
Rate 2 Min
Reset Mins/Rpt 2
or
Reset Rpts/Min 2
Proportional Band 3
or
Gain 3
Rate 3 Min
Reset Mins/Rpt 3
or
Reset Rpts/Min 3
Proportional Band 4
or
Gain 4
Rate 4 Min
Reset Mins/Rpt 4
or
Reset Rpts/Min 4
Cycle Time 1 Sec
Cycle Time 2 Sec
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
- -
1.000
0.00
- -
0
- -
1.000
0.00
1.00
- -
- -
1.000
0.00
1.00
- -
- -
1.000
0.00
1.00
- -
20
20
SP
Ramp/Program
SP Ramp Function
Ramp Time Min
Ramp Final SP
SP Rate Function
Rate Up EU/HRr
Rate Down EU/Hr
SP Program Function
Soak Deviation
Program Termination
Program End State
Key Reset/Rerun
Hot Start
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
――――
Disable
3
1000
Disable
0
0
Disable
0
Last SP
Disable
Disable
Disable
51-52-25-158, Revision 3.0
June 2022