TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
To determine the cover mounting method, look at the holes at
the top of the cover (Fig. 15). If the setscrews are raised
against the back pair of slots (toward the wall), the setscrews
are in the backplate and the stat is a conventional stat. If the
setscrews are raised into the front pair of holes, the setscrews
are in the stat body and the stat is a Quick-Mount stat.
CONVENTIONAL STAT
SETSCREWS VISIBLE
SPECIAL COVER
THERMOSTAT TOOL
CONVENTIONAL STAT
SETSCREW SLOT (2)
QUICK-MOUNT STAT
SETSCREW HOLE (2)
COVER
SETSCREWS VISIBLE
C3158
Fig. 16. Removing Cover.
Use the following procedure to replace a cover:
1. Hook slots at bottom of cover over two bottom tabs of
STANDARD COVE
R
stat (Fig. 17). Setpoint adjustment will align with
setpoint slot.
CONVENTIONAL STAT
QUICK-MOUNT STAT
SETSCREW LOCATION (2)
SETSCREW LOCATION (2)
QUICK-MOUNT STAT
STAT
SETSCREWS VISIBLE
STAT
BACKPLATE
STANDARD COVER
C3157
Fig. 15. Conventional and Quick-Mount Stats.
Removing and Replacing Covers
Cover assembly/disassembly requires Thermostat Tool
CCT735A (MQT735A). Use the following procedure to
remove a cover:
1. Locate setscrews in cover (back pair of slots for conven-
tional stat, front pair of holes for Quick-Mount stat).
2. Place Allen wrench end of Thermostat Tool through slot/
hole and into setscrew (Fig. 16).
3. Rotate Thermostat Tool clockwise until setscrew no
longer touches cover. Repeat for other setscrew.
4. Pull Cover out and down.
CONVENTIONAL
QUICK-MOUNT
STAT TAB (2)
STAT TAB (2)
CONVENTIONAL STAT
MOUNTING SLOT (2)
QUICK-MOUNT STAT
MOUNTING SLOT (2)
COVER
CONVENTIONAL STAT
SETSCREW SLOT (2)
QUICK-MOUNT STAT
SETSCREW HOLE (2)
C4110
Fig. 17. Replacing Cover.