Install Instructions
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
7. Hook keyhole slots of stat backplate over screws. Level
stat backplate and tighten screws.
STAT
BACKPLATE
KEYHOLE
SLOTS
9. Hook slots on stat cover over bottom tabs on stat
backplate. Swing stat cover up and over stat. Use
Thermostat Tool to raise stat backplate setscrews into
setscrew slots on top of cover.
Concrete Pour
Mounting in preparation for a concrete pour requires the
following equipment:
— Deep Wall Box 14001355-001 (Fig. 39)
— One of the following (Fig. 40):
• Plastic Cable Assembly 14001491-001 (one pipe),
-002 (two pipe), or -003 (three pipe) and Barb
Couplings CCT1606B (MJP1606B) (5/32 x 1/4 in.) or
CCT1628B (MJP1628B) (5/32 x 5/32 in.)
• Copper Cable Assembly 14001494-001 (one pipe),
-002 (two pipe), or -003 (three pipe)
• 1/2 in. emt conduit and 1/2 in. TW Setscrew
Connector CCT2900 (MVE2900)
— Tape Measure CCT422
— Soft Copper Tie Wire CCT2643 or Plastic Covered Wire
Ties CCT2663 (MVE2663)
— 2 in. Duct Tape CCT3349B
— Thermostat Tool CCT735A (MQT735A)
C4108
ALIGNMENT GUIDE
NO. 6–32 X 1/2 IN. SCREW (2)
FOR FINISHED WALL
C3185
PROVIDED WITH DEEP WALL BOX
Fig. 39. Deep Wall Box.
STAT
STAT
BACKPLATE
C3572
8. Mount stat to stat backplate.
95-5597—1
34