Install Instructions

TP9600-TP9630 PNEUMATIC THERMOSTATS
INSTALLATION
These instructions cover mounting the thermostat to a
wall without additional hardware. For replacement of
existing competitive and older Honeywell thermostats,
use the appropriate adapter kit and follow instructions
packed with kit.
Installation Tools
The following tools will be useful during calibration check
and cover installation:
Part No. Description (Fig. 1)
305965 Gage, 0 to 30 psi (0 to 207 kPa)
CCT729A Gage Adapter for thermostats with
gage tap fitting
CCT735A Thermostat Tool
CCT729A
305965
CCT735A
Fig. 1. Thermostat installation tools.
Remote Restrictors
When remote restrictors are required, (one pipe TP9630)
select from Figure 2.
SEE CHART FOR BARB SIZE
A B
FILTER
INLET
ALL INLET BARBS
1/4 IN. (6 MM)
REMOTE RESTRICTORS
Part No. Orifice Body
Barb Size
in inches (MM)
14002913– Size in inches Color
A B
–001* 0.005 Blue 1/4 (6)
5/32 (4)
–004 0.005 Blue 5/32 (4)
5/32 (4)
* One Barb Cap 14003567-001 Furnished with Restrictor
C3931-1
Fig. 2. Remote restrictors.
Piping
Use 5/32-in. O.D. polyethylene tubing. Connect main and
branch lines to the backplate, connecting main to the left
side barb fitting as viewed from the back and branch to the
right side barb. Leave the third (lower) fitting open.
Mounting
See Figure 3. If mounting on other than a hollow wall, see
Installation Instructions 95-5597.
THROTTLING RANGE
M11067
Fig. 3. TP9600-TP9630 thermostat with cover removed.
2
7060 80 90
ANTIHUM
SPRING (2)
THROTTLING
RANGE
ADJUSTMENT (2)
(NITE/WINTER)
SETPOINT DIAL
(NITE/WINTER)
THERMOMETER
CALIBRATION
BOBBIN
SETPOINT
INDICATOR
(NITE/WINTER)
SETPOINT
INDICATOR
CALIBRATION
SCREW
(DAY/SUMMER)
DAY/AUTO LEVER
(TP9610 ONLY)
SETPOINT INDICATOR
ADJUSTMENT
5
5
5
6
7
SCALEPLATE
MAX
MAX
SCALE (2)
(DAY/SUMMER)
THROTTLING
PLATE (2)
GAGE TAP
NOTE: NOT ALL ADJUSTMENTS ARE ON ALL THERMOSTATS.
TEMPERATURE
INDICATOR
STOPS
TEMPERATURE
SETTING
95-7550