VisionPRO 8000 Spec Sheet 2017
Table Of Contents
- Application
- Features
- Contents
- Specifications
- System Installation
- Installation Options
- Guidelines for Installing RedLINK Devices
- Installing Equipment Interface Module (if used)
- Wiring 24 Vac Common
- Selecting Discharge and Return Air Temperature Sensor Mounting Locations
- Installing Discharge and Return Air Temperature Sensors
- Selecting Thermostat Location
- Installing Wallplate
- Installing VisionPRO® 8000 with RedLINK™
- Wiring the Thermostat
- Remove Coin Cell Battery Tab
- Mounting Thermostat on Wallplate
- Power Optional RedLINK™ Accessories
- Performing Initial Setup
- Installer Tests
- Operation
- Setting the Time/Date
- Setting the Fan
- Setting System Mode
- Adjusting Program Schedules
- Overriding Schedules: Residential Use
- Overriding Schedules: Commercial Use
- Viewing Equipment Status
- Setting Vacation Hold: Residential Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Remote Setback: Commercial Use
- Adjusting Humidification Settings
- Adjusting Dehumidification Settings: Residential Use
- Adjusting Dehumidification Settings: Commercial Use
- Adjusting Ventilation Settings
- Ventilation Options
- Setting Preferences
- Cleaning the Thermostat Screen
- Adjusting Security Settings
- Viewing Dealer Information
- Advanced Features
- Installer Options
- Using the Temperature Display
- Using the Humidity Display
- Universal Outputs (U1, U2, U3)
- Universal Inputs (S1, S2, S3, S4)
- Data Logs
- Dry Contact Alerts
- Set Up the Dry Contact Alerts
- Staging Control
- Heat Pump and Backup Heat Operation
- Indoor Air Quality (IAQ) Control
- IAQ Reminders
- Customizable Reminders
- MicroSD card
- Commercial Features
- Overriding Schedules: Commercial Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Ramp Rates (Commercial Use)
- Remote Setback (Commercial Use)
- Economizer and Time of Day (TOD) Operation
- Pre-Occupancy Purge
- Battery Replacement
- Optional Accessories
- Portable Comfort Control
- Remote Indoor Sensors
- Replacing a Thermostat
- Replacing an Equipment Interface Module
- Wiring
- Zoning
- Troubleshooting
- Regulatory Information
VISIONPRO
®
8000 WITH REDLINK™
68-0312—05 50
901 Sensor for Dehum
Change to:
T-St at Sens or
Remote Indoor Sensor Name
Remote Indoor Sensor Name
Remote Indoor Sensor Name
Remote Indoor Sensor Name
Remote Indoor Sensor Name
Remote Indoor Sensor Name
(Up to 6 Remote Indoor Sensors)
T-Stat Sensor Both No Select a sensor to control dehumidification
(thermostat or an optional remote sensor). If
multiple sensors are installed, you can use a
different sensor for humidification control. See
“Dehumidification control” beginning on
page 115.
Note: Humidity sensing cannot be averaged.
902 Humidity Sensor on
Home Screen
Hum
Dehum
Hum Both No This ISU is only displayed when separate humidity
sensors are used to control humidification and
dehumidification. Only one of the sensors can be
displayed on the home screen. Select either the
Humidification Sensor or the Dehumidification
Sensor.
904 Dehum Wiring
None
U1
U2
U3
Thermostat
defaults to the
next unused
universal
terminal (U1,
U2, U3).
Both No Number of Universal Outputs:
TH8321 Thermostat: U1 terminals
Equipment Interface Module (EIM): U1, U2 and
U3 terminals
U1, U2, U3 are dry contacts that require power.
See “Wiring IAQ Equipment or a Heat/Cool Stage
to the Universal Terminals” beginning on
page 133.
905 Dehum Terminal -
U1
Dehum Terminal -
U2
Dehum Terminal -
U3
Note: The U
terminal shown on
the screen depends
on the terminal you
selected at ISU 904
(Dehum Wiring).
Normally Closed
Normally Open
Defaults to
Normally Closed
when ISU 900
Dehum
Equipment is
A/C with Low
Fan
Defaults to
Normally Open
when ISU 900
Dehum
Equipment is
Hot Gas Bypass
Both No Choose an option appropriate for the type of
equipment installed.
Normally Open: U1, U2 or U3 will normally be
open and will close when the thermostat calls for
dehumidification.
Normally Closed: U1, U2 or U3 will normally be
closed and will open when the thermostat calls for
dehumidification.
Number of Universal Outputs:
TH8321 Thermostat: U1 terminals
Equipment Interface Module (EIM): U1, U2 and
U3 terminals
907 Dehum Over
Cooling Limit
0°, 1°, 2°, 3° F
3° F Residential No This ISU is only displayed when ISU 900 Dehum
Equipment is set to A/C with Low Fan or A/C with
High Fan.
The thermostat uses the cooling system to reduce
humidity by lowering the temperature up to 3° F
below the current cool setpoint until the desired
humidity level is reached.
The thermostat keeps the temperature below the
cooling setpoint until the desired humidity level is
reached.
0° F is only an option when ISU 900 Dehum
Equipment is set to A/C with Low Fan.
908 DehumControl
Basic
Minimum On Time
Cooling Droop
Reheat
Basic Commercial No See “Dehumidification - Commercial” beginning
on page 88.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes