VisionPRO 8000 Spec Sheet 2017

Table Of Contents
VISIONPRO
®
8000 WITH REDLINK™
45 68-0312—05
604 Remote Setback
Heat Setpoint
50° F to 70° F
64° F Commercial Yes Remote Setback requires an EIM (Equipment
Interface Module).
During occupied periods, the occupancy sensor
tells the thermostat to go to setback settings when
no one is in the room. If someone is in the room,
then it follows the settings of the occupied period.
The occupancy sensor is ignored during
unoccupied periods.
If the thermostat is setup for non-programmable,
the occupancy sensor tells the thermostat to go to
setback settings when no one is in the room. If
someone is in the room, then it follows the settings
set by the user.
605 Drain Pan Alert
None
S1
S2
S3
S4
None Both Yes Dry Contact Alerts require an Equipment Interface
Module.
Select the terminals wired to the Full Drain Pan
Dry Contact Device.
606 Drain Pan Alert is
[See Settings]
Normally Open
Normally Closed
Normally Open Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of
device installed.
Normally Open: The Dry Contact device is
normally open and will close when the device
detects the drain pan is full.
Normally Closed: The Dry Contact device is
normally closed and will open when the device
detects the drain pan is full.
607 Dirty Filter Alert
None
S1
S2
S3
S4
None Both Yes Dry Contact Alerts require an Equipment Interface
Module.
Select the terminals wired to the Dirty Filter Dry
Contact Device.
608 Dirty Filtr Alert is
[See Settings]
Normally Open
Normally Closed
Normally Open Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of
device installed:
Normally Open: The Dry Contact device is
normally open and will close when the device
detects a dirty filter.
Normally Closed: The Dry Contact device is
normally closed and will open when the device
detects a dirty filter.
609 Water Leak Alert
None
S1
S2
S3
S4
None Both Yes Dry Contact Alerts require an Equipment Interface
Module.
Select the terminals wired to the Water Leak Dry
Contact Device (wet switch).
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes