VisionPRO 8000 Spec Sheet 2017
Table Of Contents
- Application
- Features
- Contents
- Specifications
- System Installation
- Installation Options
- Guidelines for Installing RedLINK Devices
- Installing Equipment Interface Module (if used)
- Wiring 24 Vac Common
- Selecting Discharge and Return Air Temperature Sensor Mounting Locations
- Installing Discharge and Return Air Temperature Sensors
- Selecting Thermostat Location
- Installing Wallplate
- Installing VisionPRO® 8000 with RedLINK™
- Wiring the Thermostat
- Remove Coin Cell Battery Tab
- Mounting Thermostat on Wallplate
- Power Optional RedLINK™ Accessories
- Performing Initial Setup
- Installer Tests
- Operation
- Setting the Time/Date
- Setting the Fan
- Setting System Mode
- Adjusting Program Schedules
- Overriding Schedules: Residential Use
- Overriding Schedules: Commercial Use
- Viewing Equipment Status
- Setting Vacation Hold: Residential Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Remote Setback: Commercial Use
- Adjusting Humidification Settings
- Adjusting Dehumidification Settings: Residential Use
- Adjusting Dehumidification Settings: Commercial Use
- Adjusting Ventilation Settings
- Ventilation Options
- Setting Preferences
- Cleaning the Thermostat Screen
- Adjusting Security Settings
- Viewing Dealer Information
- Advanced Features
- Installer Options
- Using the Temperature Display
- Using the Humidity Display
- Universal Outputs (U1, U2, U3)
- Universal Inputs (S1, S2, S3, S4)
- Data Logs
- Dry Contact Alerts
- Set Up the Dry Contact Alerts
- Staging Control
- Heat Pump and Backup Heat Operation
- Indoor Air Quality (IAQ) Control
- IAQ Reminders
- Customizable Reminders
- MicroSD card
- Commercial Features
- Overriding Schedules: Commercial Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Ramp Rates (Commercial Use)
- Remote Setback (Commercial Use)
- Economizer and Time of Day (TOD) Operation
- Pre-Occupancy Purge
- Battery Replacement
- Optional Accessories
- Portable Comfort Control
- Remote Indoor Sensors
- Replacing a Thermostat
- Replacing an Equipment Interface Module
- Wiring
- Zoning
- Troubleshooting
- Regulatory Information
VISIONPRO
®
8000 WITH REDLINK™
45 68-0312—05
604 Remote Setback
Heat Setpoint
50° F to 70° F
64° F Commercial Yes Remote Setback requires an EIM (Equipment
Interface Module).
During occupied periods, the occupancy sensor
tells the thermostat to go to setback settings when
no one is in the room. If someone is in the room,
then it follows the settings of the occupied period.
The occupancy sensor is ignored during
unoccupied periods.
If the thermostat is setup for non-programmable,
the occupancy sensor tells the thermostat to go to
setback settings when no one is in the room. If
someone is in the room, then it follows the settings
set by the user.
605 Drain Pan Alert
None
S1
S2
S3
S4
None Both Yes Dry Contact Alerts require an Equipment Interface
Module.
Select the terminals wired to the Full Drain Pan
Dry Contact Device.
606 Drain Pan Alert is
[See Settings]
Normally Open
Normally Closed
Normally Open Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of
device installed.
Normally Open: The Dry Contact device is
normally open and will close when the device
detects the drain pan is full.
Normally Closed: The Dry Contact device is
normally closed and will open when the device
detects the drain pan is full.
607 Dirty Filter Alert
None
S1
S2
S3
S4
None Both Yes Dry Contact Alerts require an Equipment Interface
Module.
Select the terminals wired to the Dirty Filter Dry
Contact Device.
608 Dirty Filtr Alert is
[See Settings]
Normally Open
Normally Closed
Normally Open Both Yes Dry Contact Alerts require an EIM (Equipment
Interface Module).
Choose an option appropriate for the type of
device installed:
Normally Open: The Dry Contact device is
normally open and will close when the device
detects a dirty filter.
Normally Closed: The Dry Contact device is
normally closed and will open when the device
detects a dirty filter.
609 Water Leak Alert
None
S1
S2
S3
S4
None Both Yes Dry Contact Alerts require an Equipment Interface
Module.
Select the terminals wired to the Water Leak Dry
Contact Device (wet switch).
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes