VisionPRO 8000 Spec Sheet 2017

Table Of Contents
VISIONPRO
®
8000 WITH REDLINK™
68-0312—05 32
314 Cool / Compressor
Cycles Per Hour
Stage 1
Note: “Stage 1" is
not displayed if
there is only 1
stage.
1 to 6 CPH
3 Both No This ISU is only displayed when ISU 207 Cool /
Compressor Stages is set to 1 stage.
Cycle rate limits the maximum number of times
the system can cycle in a 1 hour period measured
at a 50% load. For example, when set to 3 CPH, at
a 50% load, the most the system will cycle is 3
times per hour (10 minutes on, 10 minutes off).
The system cycles less often when load conditions
are less than or greater than a 50% load.
314 Cool / Compressor
Cycles Per Hour
Stage 2
1 to 6 CPH
3 Both No This ISU is only displayed when ISU 207 Cool /
Compressor Stages is set to 2 stages.
Cycle rate limits the maximum number of times
the system can cycle in a 1 hour period measured
at a 50% load. For example, when set to 3 CPH, at
a 50% load, the most the system will cycle is 3
times per hour (10 minutes on, 10 minutes off).
The system cycles less often when load conditions
are less than or greater than a 50% load.
314 Cool Cycles Per
Hour Stage 3
1 to 6 CPH
3 Commercial No This ISU is only displayed when ISU 101
Application is set to Commercial and ISU 207 Cool
Stages is set to 3 stages.
Cycle rate limits the maximum number of times
the system can cycle in a 1 hour period measured
at a 50% load. For example, when set to 3 CPH, at
a 50% load, the most the system will cycle is 3
times per hour (10 minutes on, 10 minutes off).
The system cycles less often when load conditions
are less than or greater than a 50% load.
314 Cool Cycles Per
Hour Stage 4
1 to 6 CPH
3 Commercial Yes This ISU is only displayed when ISU 101
Application is set to Commercial and ISU 207 Cool
Stages is set to 4 stages.
Cycle rate limits the maximum number of times
the system can cycle in a 1 hour period measured
at a 50% load. For example, when set to 3 CPH, at
a 50% load, the most the system will cycle is 3
times per hour (10 minutes on, 10 minutes off).
The system cycles less often when load conditions
are less than or greater than a 50% load.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes