VisionPRO 8000 Spec Sheet 2017
Table Of Contents
- Application
- Features
- Contents
- Specifications
- System Installation
- Installation Options
- Guidelines for Installing RedLINK Devices
- Installing Equipment Interface Module (if used)
- Wiring 24 Vac Common
- Selecting Discharge and Return Air Temperature Sensor Mounting Locations
- Installing Discharge and Return Air Temperature Sensors
- Selecting Thermostat Location
- Installing Wallplate
- Installing VisionPRO® 8000 with RedLINK™
- Wiring the Thermostat
- Remove Coin Cell Battery Tab
- Mounting Thermostat on Wallplate
- Power Optional RedLINK™ Accessories
- Performing Initial Setup
- Installer Tests
- Operation
- Setting the Time/Date
- Setting the Fan
- Setting System Mode
- Adjusting Program Schedules
- Overriding Schedules: Residential Use
- Overriding Schedules: Commercial Use
- Viewing Equipment Status
- Setting Vacation Hold: Residential Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Remote Setback: Commercial Use
- Adjusting Humidification Settings
- Adjusting Dehumidification Settings: Residential Use
- Adjusting Dehumidification Settings: Commercial Use
- Adjusting Ventilation Settings
- Ventilation Options
- Setting Preferences
- Cleaning the Thermostat Screen
- Adjusting Security Settings
- Viewing Dealer Information
- Advanced Features
- Installer Options
- Using the Temperature Display
- Using the Humidity Display
- Universal Outputs (U1, U2, U3)
- Universal Inputs (S1, S2, S3, S4)
- Data Logs
- Dry Contact Alerts
- Set Up the Dry Contact Alerts
- Staging Control
- Heat Pump and Backup Heat Operation
- Indoor Air Quality (IAQ) Control
- IAQ Reminders
- Customizable Reminders
- MicroSD card
- Commercial Features
- Overriding Schedules: Commercial Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Ramp Rates (Commercial Use)
- Remote Setback (Commercial Use)
- Economizer and Time of Day (TOD) Operation
- Pre-Occupancy Purge
- Battery Replacement
- Optional Accessories
- Portable Comfort Control
- Remote Indoor Sensors
- Replacing a Thermostat
- Replacing an Equipment Interface Module
- Wiring
- Zoning
- Troubleshooting
- Regulatory Information
VISIONPRO
®
8000 WITH REDLINK™
23 68-0312—05
201 Heating Equipment
Heat Pump:
Air to Air Heat Pump
Geothermal
Geothermal Radiant
Air to Air Heat
Pump
Both No This ISU is not displayed when ISU 200 Heating
System is set to Conv. Forced Air, Radiant Heat,
Other or None (Cool Only).
See “Geothermal Radiant Heat” beginning on
page 79.
203 Radiant Stage 1
None
U1
U2
U3
Default varies
based on
previous
selections
Both No This ISU is only displayed when ISU 201 Heating
Equipment is Geothermal Radiant.
Geothermal Radiant Heat must be wired to a
universal terminal (U1, U2, or U3).
U1, U2 and U3 are normally open dry contacts
when configured for a stage of Heat. U1, U2 and
U3 require power from the system transformer or a
separate transformer.
U2 and U3 are only available on the Equipment
Interface Module (EIM).
204 Radiant Stage 2
None
U1
U2
U3
Default varies
based on
previous
selections
Both No This ISU is only displayed when ISU 201 Heating
Equipment is Geothermal Radiant.
Geothermal Radiant Heat must be wired to a
universal terminal (U1, U2, or U3).
U1, U2 and U3 are normally open dry contacts
when configured for a stage of Heat. U1, U2 and
U3 require power from the system transformer or a
separate transformer.
U2 and U3 are only available on the Equipment
Interface Module (EIM).
205 Geo Forced Air
None
Cooling Only
Heating and Cooling
Heating and
Cooling
Both No This thermostat has the capability of controlling
Geothermal Radiant Heat, Geothermal Forced Air
and Backup Heat.
If this thermostat is not controlling the
Geothermal Forced Air System, select None. This
setting is typically used if the thermostat is only
controlling Geothermal Radiant Heat.
If this thermostat is using the Geothermal Forced
Air System for cooling and not for heating, select
Cooling Only.
If this thermostat is using the Geothermal Forced
Air System for both heating and cooling, select
Heating and Cooling.
206 Reversing Valve
O (O/B on Cool)
B (O/B on Heat)
O/B on Cool Both No Only displayed if the equipment type is Air to Air
Heat Pump, Geothermal or Geothermal Radiant.
207 Cool Stages /
Compressor Stages
1-4
1 if ISU 101 is
Residential
2 if ISU 101 is
Commercial
Both No Conventional:
Cool Stage 3 and 4 are only available if ISU 101 is
Commercial.
Cool Stage 3 and 4 must be wired to a universal
terminal (U1, U2 or U3).
Heat Pumps:
Maximum of 2 Compressor Stages for heat pump
systems.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes