3. Select Normally Open when Occupied or Normally
Closed when Occupied based on the type of dry con-
tact device installed.
NOTE: Normally Open when Occupied: The Dry
Contact device is open when the room is
occupied and will close when the room is
unoccupied.
Normally Closed when Occupied: The Dry
Contact device is closed when the room is
occupied and will open when the room is
unoccupied.
Fig. 293.
4. Select a Remote Setback Time Delay. The Remote
Setback Time Delay forces the thermostat to wait
before it switches from occupied settings to the
Remote Setback settings. When set to 0 minutes, the
thermostat will switch from occupied settings to the
Remote Setback settings immediately when the room
is unoccupied.
Fig. 294.
5. Select the Remote Setback settings that you would
like to maintain when the occupancy sensor detects
the room is unoccupied.
Fig. 295.
Economizer and Time of Day (TOD)
Operation
Economizer
The thermostat controls an economizer module to provide
ventilation during occupied periods and free cooling when
outdoor conditions are favorable. In some climates the
cooling system may run several hours when it may not be
required to maintain indoor comfort. When outdoor
conditions are favorable, ventilation with outdoor air can
achieve the same level of comfort at lower cost. Table 5
explains how the Economizer Module is controlled by the
thermostat.
The thermostat works with the W7220, W7212, W7213 and
W7214 Economizer Modules for both heat pump and
conventional systems.