VisionPRO 8000 Spec Sheet 2017
Table Of Contents
- Application
- Features
- Contents
- Specifications
- System Installation
- Installation Options
- Guidelines for Installing RedLINK Devices
- Installing Equipment Interface Module (if used)
- Wiring 24 Vac Common
- Selecting Discharge and Return Air Temperature Sensor Mounting Locations
- Installing Discharge and Return Air Temperature Sensors
- Selecting Thermostat Location
- Installing Wallplate
- Installing VisionPRO® 8000 with RedLINK™
- Wiring the Thermostat
- Remove Coin Cell Battery Tab
- Mounting Thermostat on Wallplate
- Power Optional RedLINK™ Accessories
- Performing Initial Setup
- Installer Tests
- Operation
- Setting the Time/Date
- Setting the Fan
- Setting System Mode
- Adjusting Program Schedules
- Overriding Schedules: Residential Use
- Overriding Schedules: Commercial Use
- Viewing Equipment Status
- Setting Vacation Hold: Residential Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Remote Setback: Commercial Use
- Adjusting Humidification Settings
- Adjusting Dehumidification Settings: Residential Use
- Adjusting Dehumidification Settings: Commercial Use
- Adjusting Ventilation Settings
- Ventilation Options
- Setting Preferences
- Cleaning the Thermostat Screen
- Adjusting Security Settings
- Viewing Dealer Information
- Advanced Features
- Installer Options
- Using the Temperature Display
- Using the Humidity Display
- Universal Outputs (U1, U2, U3)
- Universal Inputs (S1, S2, S3, S4)
- Data Logs
- Dry Contact Alerts
- Set Up the Dry Contact Alerts
- Staging Control
- Heat Pump and Backup Heat Operation
- Indoor Air Quality (IAQ) Control
- IAQ Reminders
- Customizable Reminders
- MicroSD card
- Commercial Features
- Overriding Schedules: Commercial Use
- Setting Holiday/Event Schedules: Commercial Use
- Setting Custom Events: Commercial Use
- Setting Holiday Schedule: Commercial Use
- Setting Holiday Override: Commercial Use
- Initiating Occupancy Mode: Commercial Use
- Ramp Rates (Commercial Use)
- Remote Setback (Commercial Use)
- Economizer and Time of Day (TOD) Operation
- Pre-Occupancy Purge
- Battery Replacement
- Optional Accessories
- Portable Comfort Control
- Remote Indoor Sensors
- Replacing a Thermostat
- Replacing an Equipment Interface Module
- Wiring
- Zoning
- Troubleshooting
- Regulatory Information
VISIONPRO
®
8000 WITH REDLINK™
35 68-0312—05
316 Backup Heat Cycles
Per Hour Stage 2
1 to 12 CPH
Electric =
9 CPH
Gas / Oil =
5 CPH
Both No This ISU is only displayed when ISU 207 or 213
Backup Heat Stages is set to 2 stages.
Cycle rate limits the maximum number of times
the system can cycle in a 1 hour period measured
at a 50% load. For example, when set to 3 CPH, at
a 50% load, the most the system will cycle is 3
times per hour (10 minutes on, 10 minutes off).
The system cycles less often when load conditions
are less than or greater than a 50% load. The
recommended cycle rate settings are below for
each heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH
High Efficiency Gas Forced Air = 3 CPH
Oil Forced Air = 5 CPH
Electric Forced Air = 9 CPH
Hot Water Fan Coil = 3 CPH
Hot Water Radiant Heat = 3 CPH
Geothermal Radiant Heat = 3 CPH
Steam = 1 CPH
Gravity = 1 CPH
324 Compressor Off
Time
Off
1 - 5 minutes
5 minutes Both No The thermostat has a built in compressor
protection (minimum off timer) that prevents the
compressor from restarting too early after a
shutdown. The minimum-off timer is activated
after the compressor turns off.
If there is a call during the minimum-off timer, the
thermostat shows “Wait” in the display.
326 Extended Fan Run
Time in Cool
0, 30, 60, 90 seconds, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11, 12, 13, 14, 15
minutes
0 seconds Both No After the call for cooling ends, the thermostat
keeps the fan on for the selected amount of time
for increased efficiency. This may re-introduce
humidity into the living space.
326 Extended Fan Run
Time in Heat
0, 30, 60, 90 seconds, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11, 12, 13, 14, 15
minutes
0 seconds Both No After the call for heating ends, the thermostat
keeps the fan on for the selected amount of time
for increased efficiency.
400 Scheduled Periods
2 or 4 periods per day
4 periods per
day
Both No Residential:
4 Periods = Wake, Leave, Return, Sleep
2 Periods = Wake, Sleep
Commercial:
4 Periods = Occupied 1, Unoccupied 1, Occupied
2, Unoccupied 2
2 Periods = Occupied 1, Unoccupied 1
401 Pre-Occupancy
Purge
Off
1 hour
2 hour
3 hour
Off Commercial No Runs the fan 1 to 3 hours before each occupied
period to provide a comfortable workplace upon
arrival.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes