Honeywell-TH6220WF2006-Install-Instructions

4
Setting Slider Tabs
Set R Slider Tab, see Figure 9.
Use built-in jumper (R Slider Tab)
to differentiate between one or two
transformer systems.
If there is only one R wire, and it is
connected to the R, Rc, or RH terminal
on the old thermostat, set the slider to
the up position (1 wire).
If there is one wire connected to the R
terminal and one wire connected to the
Rc terminal, set the slider to the down
position (2 wires).
Set U Slider Tab, see Figure 10.
Use built-in jumper (U Slider Tab)
of universal relay to wire ventilation.
Please note that ventilation is not
supported on all models.
When the U Slider Tab is in the down
position (2 wires) the U contacts are a
dry set of contacts.
If the ventilator is powered by the
cooling transformer, move the jumper
switch to the up position (1 wire). With
this switch set to 1 wire, the lower U
terminal is internally jumped to the Rc
terminal. In this application, hook up
one wire from the vent damper to the U
terminal and the other to the common
side of the cooling system transformer.
10
9