Installation Manual
PRO TH2000DH/TH1000E1/TH1000DH Series
7
69-2609EFS—13
ENGLISH
Setup function Settings & options (factory default in bold)
5 Heating cycle rate
(CPH: cycles/hour)
TH2110DH, TH1110E1,
TH1110DH and
TH1100DH
5 For gas or oil furnaces of less than 90% efficiency
1 For steam or gravity systems
3 For hot water systems & furnaces of over 90% efficien-
cy
6 For electric furnaces
[Other cycle rate options: 2 or 4 CPH]
6 Auxiliary heat
cycle rate (CPH)
TH2210DH and
TH1210DH
5 For gas or oil furnaces of less than 90% efficiency
1 For steam or gravity systems
3 For hot water systems & furnaces of over 90% efficiency
6 For electric furnaces
[Other cycle rate options: 2 or 4 CPH]
9 Compressor
cycle rate (CPH)
3 Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5, or 6 CPH]
13 Early Start (TH2110DH
and TH2210DH)
1 On **See page 8
0 Off
14 Temperature
display
0 Fahrenheit
1 Celsius
15 Compressor
protection
1 Five-minute compressor off time (See page 8)
0 No compressor off time
20 Clock display
(TH2110DH and
TH2210DH)
0 12-hour display
1 24-hour display
25 Lower temperature
range (TH1100DH only)
0 Standard range 40°F to 90°F (4.5°C to 32°C)
1 Lower range (for garage mode) 35°F to 90°F
(1.5°C to 32°C)
40 Restore program
schedule to default
(TH2110DH and
TH2210DH)
0 Off
1 On - program schedule default settings are listed in the
operating manual
Installer setup
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection is bypassed during testing. To prevent equipment damage,
avoid cycling the compressor quickly.