T822/TS822 Spec Sheet
Table Of Contents
T822, TS822 HEATING/COOLING THERMOSTATS
68-0095-2 2
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
SPECIFICATIONS
The specifications given in this publication do not include
normal manufacturing tolerances. Therefore, this unit may not
exactly match the listed specifications. Also, this product is
tested and calibrated under closely controlled conditions, and
some minor differences in performance can be expected if
those conditions are changed.
TRADELINE® MODELS
TRADELINE® models are selected and packaged for ease of
handling, ease of stocking, and maximum replacement value.
TRADELINE® specifications are the same as those of
standard models except as follows:
Tradeline Models Available:
T822D Heating Thermostat used for low voltage heating appli-
cations with adjustable heat anticipator.
TS822A Heating Thermostat used for 250/500 and 750 mV
applications with nonadjustable heat anticipator.
Additional Features:
• T822D and TS822A available with positive Off.
• T822D models available with heat anticipator factory set at
0.2A for electric heat applications.
• Temperature range stops available on some TRADELINE
models.
STANDARD MODELS
Standard Models Available:
T822A Heating Thermostat used in low voltage heating appli-
cations. Nonadjustable heating anticipator.
T822C Cooling Thermostat used in low voltage cooling appli-
cations. Nonadjustable cooling anticipator.
T822D Heating Thermostat used in low voltage heating appli-
cations. Adjustable heat anticipator.
T822F Heating Thermostat used in low voltage heating appli-
cations. Adjustable heat anticipator and On-Auto Fan
switching.
T822G Heating or Cooling Thermostat used in low voltage
heating or cooling applications. Works with series 20
heating applications. Adjustable heat anticipator.
Nonadjustable cooling anticipator.
TS822A Heating Thermostat used in millivoltage heating
applications.
Electrical Ratings:
T822A: 0 to 1.2A at 30 Vac; 1.5A at 24 Vdc.
T822C: 1.0A running, 5.0A inrush at 25 Vac.
T822D,F,G: 0.18 to 0.8A at 30 Vac/Vdc.
TS822A: 0.1A at 250/500 and 750 mV.
Anticipator Ratings:
T822A: Nonadjustable. Factory set from 0 to 0.4A.
T822C: Nonadjustable. Factory set from 0 to 1.0A.
T822D: Adjustable from 0.18 to 1.0A or 0.3 to 1.2A.
T822F: Adjustable from o.18 to 1.0A.
T822G:
Heating Anticipator: Adjustable from 0.18 to 1.0A.
Cooling Anticipator: Nonadjustable. Factory set from 0 to
1.0A.
Switching:
Heating Thermostats: Spst mercury switch makes R to W on
temperature fall.
Cooling Thermostats: Spst mercury switch makes R to Y on
temperature rise.
Temperature Setting Range (Specify When Ordering):
Standard Heating Models: 55° F to 95°F (13°C to 35 °C).
Positive Off Heating Models: 60° F to 95°F (16°C to 35°C).
Standard Cooling Models: 55° F to 95°F (13 °C to 35°C).
Positive Off Cooling Models: 55° F to 85°F.13°C to 29°C).
Dimensions: See Fig. 1.
Mounting Means: Two screws through thermostat mounting
holes to wall or vertical or horizontal mounting box.
Optional Specifications:
Positive Off Switch: Temperature setpoint lever provides
complete control circuit shutdown. Does not replace power
supply disconnect switch.
Adjustable Range Stops: Limits setpoint temperature range.
Accessories:
104944A Calibration Wrench.
193121A Mounting Plate to mount thermostat on horizontal or
vertical outlet box.