Install Instructions
Table Of Contents
T775P SERIES 2000 CONTROLLER 1. SETUP
62-0256–03 20
Fig. 41. Setup - Outputs - Options - Show Runtime.
1.3.3.10. SHOW RT (show run time hours)
1. Press the X button to display the Show RT values.
2. Use the S and T buttons to select YES or NO.
Default: YES
3. Press the X button to accept the value and return to
the Options menu.
Selecting YES shows the RT (run time) hours for the first
four stages on the home screen displays. Stages 5-12 are
not displayed.
NOTE: Run times can be reset to zero for the first four
(4) stages. You must do this for each of the
stages (1-4) that you want to reset to zero. See
“1.3.4.1.1. RESET RT (run time)” on page 21.
Fig. 42. Setup - Outputs - Options - Exit.
1.3.3.11. Exit Options Setup
Press the W button (or highlight EXIT and press the X
button) to exit and return to the Outputs menu.
Fig. 43. Setup - Outputs - Stage Menu.
1.3.4. Setting up the Stages
1. From the Outputs menu, use the S and T buttons
to highlight the desired Stage.
2. Press the X button to display the selected Stage
menu.
NOTES:
1. Only the first four (4) stages have run time
reset options.
2. The relay outputs are used as stages with the
last relay available to be configured as the
pump output. See Table 4 on page 11.
Fig. 44. Setup - Outputs - Stage.
1.3.4.1. STAGE
The first four (4) stages have one setup option, Reset
Runtime. This option displays only if Show RT is
configured in Setup (see Fig. 41).
1. From the Stage menu, use the S and T buttons to
highlight the RESET RT option.
2. Press the X button to display the option.
SHOW
RUN TIME
FOR BOILER
STAGES
SETUP
OUTPUTS
OPTIONS
SHOW RT
M24668
YES
NO
SETUP
OUTPUTS
OPTIONS
SHOW RT
SETUP
OUTPUT
OPTIONS
M24669
RESET
INTEGRAL
DERIVATIV
ON DELAY
OFF DELAY
WWSD
LEAD LAG
DI OPTS
SHOW RT
EXIT
SETUP
OUTPUTS
M24670
# STAGES
SCHEDULE
OPTIONS
STAGE 1
STAGE 2
STAGE 3
STG4/PUMP
EXIT
SETUP
OUTPUTS
SETUP
OUTPUTS
STAGE 1
M24671
RESET RT
EXIT
SETUP
OUTPUTS
STAGE 1