Submittal Sheet
Table Of Contents
- Product Description
- Before Installation
- Installation and Setup
- Mounting
- Wiring
- Wiring Application Examples
- Checkout
- Interface Overview
- Programming Overview
- 1. Setup
- 2. Programming Output (Loops and Additional Relays) with No Reset
- 3. Programming Output (Loops and Additional Relays) with Reset
- 4. Scheduling
- Summary Menu
- Troubleshooting
- Specifications
- DoC
2. PROGRAMMING OUTPUT (LOOPS AND ADDITIONAL RELAYS) WITH NO RESET T775L SERIES 2000 CTLR
23 62-0257–05
Fig. 54. Program - Throttling Range or Differential.
2.2.2. THROTTLING RANGE or DIFFERENTIAL
Throttling Range is used for Loops, and Differential
displays for the Relay outputs.
1. From the menu, use the S and T buttons to high-
light THROT RNG or DIFFRNTL.
2. Press the X button to display the throttling range
value.
3. Use the S and T buttons to increase/decrease the
desired value.
Default: 20°F (-6.6°C)
Range: 1°F to 150°F (1°C to 66°C)
4. Press the X button to accept the value and display
the next option.
The number of degrees selected for the throttling range is
divided between the number of stages. See page 11 for
staged operation.
In heating mode, the Differential is below the setpoint.
The relay de-energizes when the temperature rises to the
setpoint. As the temperature drops to the setpoint minus
the Differential, the relay energizes.
In cooling mode, the Differential is above the setpoint.
The relay de-energizes when the temperature falls to the
setpoint. As the temperature rises to the setpoint plus the
Differential, the relay energizes.
Fig. 55. Program - Sensor.
2.2.3. SENSOR
1. From the menu, use the S and T buttons to high-
light SENSOR.
2. Press the X button to display the sensor selections.
3. Use the S and T buttons to select Sensor A or B.
4. Press the X button to accept the highlighted sensor
and display the next option.
Fig. 56. Program - Heat/Cool.
2.2.4. HEAT/COOL
1. From the menu, use the S and T buttons to high-
light HEAT/COOL.
Default: HEAT
2. Press the X button to display the heat and cool
selections.
3. Use the S and T buttons to select Heat or Cool.
4. Press the X button to accept the highlighted selec-
tion and display the next option.
ENTER
THROTTLING
RANGE FOR
LOOP 1
PROGRAM
LOOP 1
THROT RNG
MENU
PROGRAM
LOOP 1
THROT RNG
20
F
o
M24423
MENU
PROGRAM
LOOP 1
SENSOR
SELECT
SENSOR
FOR
LOOP 1
SENSOR A
SENSOR B
PROGRAM
LOOP 1
SENSOR
M24424
PROGRAM
LOOP 1
HEAT/COOL
MENU
PROGRAM
LOOP 1
HEAT/COOL
SELECT
HEAT/COOL
FOR
LOOP 1
HEAT
COOL
M24425