Submittal Sheet

T775L SERIES 2000 CTLR 2. PROGRAMMING OUTPUT (LOOPS AND ADDITIONAL RELAYS) WITH NO RESET
62-0257–05 22
2. PROGRAMMING OUTPUT (LOOPS
AND ADDITIONAL RELAYS) WITH
NO RESET
The T775L can be programmed for Reset or No Reset.
From the factory, the T775L is programmed for No Reset.
This section describes the steps necessary to program
the controller for No Reset. Continue with “2.1. Entering
Program Mode”.
If you are employing Reset, go to “3. Programming Output
(Loops and Additional Relays) with Reset” on page 24.
Fig. 51. Program Menu.
2.1. Entering Program Mode
Press the MENU button, then select PROGRAM and
press the X button to view the Program menu.
Fig. 52. Program Menus - No Reset.
2.2. Program Menu for Outputs with No Reset
From the Program menu, highlight the Loop or Relay
desired and press the X button to view the parameters.
Fig. 52 shows both the Loop and Relay menus.
NOTE: The Setback parameter displays only if
scheduling is enabled (see Fig. 31 on page 15)
or the DI Option is set to Setback. (see Fig. 33
on page 16).
Continue with “2.2.1. SETPOINT”.
Fig. 53. Program - Setpoint.
2.2.1. SETPOINT
1. From the menu, use the S and T buttons to high-
light SETPOINT.
2. Press the X button to display the setpoint value.
3. Use the S and T buttons to increase/decrease the
desired setpoint temperature.
Default: 70°F (21°C)
Range: -40°F to 248°F (-40°C to 120°C)
4. Press the X button to accept the setpoint tempera-
ture and display the next option.
MENU
PROGRAM
MENU
PROGRAM
LOOP 1
LOOP 2
RELAY 9
RELAY 10
EXIT
M24401
PROGRAM
LOOP 1
LOOPS MENU
MENU
PROGRAM
LOOP 1
SETPOINT
THROT RNG
SENSOR
HEAT/COOL
SETBACK
EXIT
ADDITIONAL RELAYS
MENU
MENU
PROGRAM
RELAY 9
SETPOINT
DIFFRNTL
SENSOR
HEAT/COOL
SETBACK
EXIT
M24421
PROGRAM
RELAY 9
ENTER
SETPOINT
FOR
LOOP 1
PROGRAM
LOOP 1
SETPOINT
MENU
PROGRAM
LOOP 1
SETPOINT
70
F
o
M24422