T775L SERIES 2000 CTLR 1. SETUP
62-0257–05 20
Fig. 44. Setup - Outputs - Loop 1 - Exit.
1.3.4.8. Exit Loop Setup
Use the S and T buttons to highlight EXIT and press the
X button.
If you have additional relay outputs, continue with “1.3.5.
Setting up the Relays”. Otherwise, go to “1.4. Exiting
Setup” on page 21
Fig. 45. Setup - Outputs - Relay Menu.
1.3.5. Setting up the Relays
1. From the Outputs menu, use the S and T buttons
to highlight the desired relay.
2. Press the X button to display the selected relay
menu.
NOTE: There can be up to two additional relays.
For example: If there are 12 total relays, and
Loop 1 uses relays 1–4, and Loop 2 uses relays
5–8, the two available additional relays will be 9
and 10. (In this example, relays 11 and 12 are
not usable since there can be only two additional
relays.)
Continue with the remainder of this section to setup the
relay outputs.
Fig. 46. Setup - Outputs - Relay - Schedule.
1.3.5.1. SCHEDULE
This selection displays only if “Use Sched = YES” is
selected during the Output Options setup (see page 15).
When selected, individual outputs default to follow the
schedule.
1. Press the X button to display the Schedule values.
2. Use the S and T buttons to select YES or NO.
Default: YES
3. Press the X button to accept the value and return to
the Relay menu.
NOTE: If USE SCHED = YES, then the default is YES.
See “1.3.3.1. USE SCHED” on page 15.
An individual output can be selected to be controlled or
not controlled by the schedule.
If NO is selected, the Setback selection does not appear
in the Program menu for this output.
SETUP
OUTPUTS
LOOP 1
SETUP
OUTPUTS
LOOP 1
# RELAYS
INTEGRAL
DERIVATIVE
ON DELAY
OFF DELAY
SCHEDULE
RESET
EXIT
M24453
SETUP
OUTPUTS
RELAY 9
SETUP
OUTPUTS
RELAY 9
SCHEDULE
RESET
RESET RT
EXIT
M24454
SETUP
OUTPUTS
RELAY 9
SCHEDULE
SETUP
OUTPUTS
RELAY 9
SCHEDULE
USE
SCHEDULE
FOR
OUTPUTS
YES
NO
M24455