Submittal Sheet

1. SETUP T775L SERIES 2000 CTLR
19 62-0257–05
Fig. 41. Setup - Outputs - Loop 1 - Off Delay.
1.3.4.5. OFF DELAY
This is the minimum time delay between consecutive OFF
stages.
1. From the Loop 1 menu, use the Sand T buttons to
highlight OFF DELAY, then press the X button to
display the interstage off delay.
2. Use the S and T buttons to change the off delay
time.
Default: 0 (zero) seconds
Range: 0 to 3,600 seconds in 10 second
increments
There is a built-in minimum delay of 1 second
between stages upon energizing.
3. Press the X button to accept the value and display
the Loop 1 menu.
Fig. 42. Setup - Outputs - Loop 1 - Schedule.
1.3.4.6. SCHEDULE
The Schedule option displays only if the USE SCHED
parameter is set to Yes (see Fig. 31 on page 15).
1. From the Loop 1 menu, use the Sand T buttons to
highlight SCHEDULE.
2. Press the X button to display the value.
3. Use the S and T buttons to select YES or NO.
Default: YES
4. Press the X button to accept the value and display
the Loop 1 menu.
An individual output can be selected to be controlled or
not controlled by the schedule. If NO is selected, the
Setback selection does not appear in the Program menu
for this output.
Fig. 43. Setup - Outputs - Loop 1 - Reset.
1.3.4.7. RESET (Loop Reset)
This selection enables the controller’s Reset function, and
allows each output to be individually programmed for
Reset or No Reset.
IMPORTANT
To use the Reset function of the controller, the
first loop must be set for Reset.
The RESET choice is offered for all outputs in setup
mode, and you can set any or all of them for Reset=YES
or Reset=NO. The default is Reset=NO.
For the remaining outputs, if Reset=YES, then these
outputs use the reset curve programmed for the first
output.
1. From the Loop 1 menu, use the Sand T buttons to
highlight RESET.
2. Press the X button to display the value.
Default: NO
3. Use the S and T buttons to select the value.
4. Press the X button to accept the value and display
the Loop 1 menu.
If you select YES, then the second loop (and any
additional relays) display this Setup option.
If you select NO, then No Reset is configured.
SETUP
OUTPUTS
LOOP 1
OFF DELAY
SETUP
OUTPUTS
LOOP 1
OFF DELAY
0
SEC
ENTER
TIME FOR
INTER-
STAGE
OFF DELAY
M24450
SETUP
OUTPUTS
LOOP 1
SCHEDULE
SETUP
OUTPUTS
LOOP 1
SCHEDULE
USE
SCHEDULE
FOR
LOOP 1
YES
NO
M24451
SETUP
OUTPUTS
LOOP 1
RESET
SETUP
OUTPUTS
LOOP 1
RESET
USE
RESET
FOR
LOOP 1
YES-BOILER
YES-OTHER
NO
M24452