T775L SERIES 2000 CTLR 1. SETUP
62-0257–05 16
Fig. 32. Setup - Outputs - Options - Min Off Time.
1.3.3.2. MIN OFF (minimum off time for all relays)
This is the minimum number of seconds of “off time” for
all relays that are not configured in a loop.
1. Press the X button to display the Min Off value.
2. Use the S and T buttons to increase/decrease the
desired number of seconds from 0 to 990 seconds
in 10 second increments.
Default: 0 (zero)
Range: 0 to 990 seconds
3. Press the X button to accept the seconds and
display the DI OPTS menu.
NOTES:
1. The minimum off time applies to all relay
outputs.
2. When minimum off time is active, relays waiting
to be energized display a flashing square
underneath the relay number on the home
screen.
3. If the minimum off time is not equal to zero (0),
the minimum off time activates at power-up.
4. To manually override, press the W button.
Fig. 33. Setup - Outputs - Options - DI Options.
1.3.3.3. DI OPTIONS (digital input options)
The DI Option that you select applies to all outputs. This
option overrides any Setpoint/Setback values entered in
the Schedule.
1. Press the X button to display the DI Option
selections.
2. Use the S and T buttons to highlight DISABLE,
SETBACK, or IGNORE.
Default: DISABLE
3. Press the X button to accept the value and display
the SHOW RT menu.
When the digital input (DI) closes, all outputs follow the DI
option value (Disable, Setback, or Ignore):
• DISABLE disables the outputs; relays return to de-
energized state.
• SETBACK enables a setback temperature value to be
programmed for each output.
— To program the Setback temperature without
Reset, see Fig. 57 on page 24.
— To program the Setback temperature with Reset,
see Fig. 68 on page 28.
• IGNORE causes the digital input to have no effect on
the Relay outputs.
Fig. 34. Setup - Outputs - Options - Show Runtime.
1.3.3.4. SHOW RT (show run time hours)
1. Press the X button to display the Show RT values.
2. Use the S and T buttons to select YES or NO.
Default: YES
3. Press the X button to accept the value and return to
the Options menu.
A limited feature in the T775L, selecting YES shows the
run time hours only of independent relays if they are
among the first four relays. Runtime of relays in a loop
cannot be shown.
NOTE: Run times can be reset to zero for each of the
first four independent relays. You must do this for
each relay that you want to reset to zero. See
“1.3.5.3. RESET RT (Run Time)” on page 21.
SETUP
OUTPUTS
OPTIONS
MIN OFF
SETUP
OUTPUTS
OPTIONS
MIN OFF
0
SEC
ENTER
MINIMUM
OFF TIME
FOR
OUTPUTS
M24441
SETUP
OUTPUTS
OPTIONS
DI OPTS
SETUP
OUTPUTS
OPTIONS
DI OPTS
SELECT DI
OPTION
FOR
RELAYS
DISABLE
SETBACK
IGNORE
M24442
SETUP
OUTPUTS
OPTIONS
SHOW RT
SETUP
OUTPUTS
OPTIONS
SHOW RT
SHOW
RUN TIME
FOR
RELAYS
YES
NO
M24443