Brochure
Table Of Contents
- TABLE OF CONTENTS
- T775 APPLICATION TIPS
- COMPATIBLE COMPONENTS
- FEATURES
- T775 OPERATIONS
- T775 APPLICATIONS
- Water Source Heat Pump Loop Water Controller - T775B
- Chiller - T775B
- Chiller, Rotary Compressor - T775B
- Cooling Tower Control - T775B2040
- Time-based Control of Fan, Pump, etc. - T775 (all models)
- Damper or Valve Modulation - T775M or T775R
- Hot Water Reset - T775R
- Chilled Water Reset - T775R
- Multi-Stage Boiler Control (No Reset) - T775P
- Multi-Stage Boiler Control (Reset) - T775P
- Multi-Stage Boiler Control (Reset) (continued)
- Multi-Stage Chiller Control (No Reset) - T775P
- 4 Stage with Pump Output and Reset - T775P using a T775S Expansion Module
- 4 Stage with Pump Output and Reset (continued)
- 3 Stage Reciprocating Chiller - T775L
- 4 Stage Heat and 6 Stage Cool - T775L
- 4 Stage Heat and 6 Stage Cool (continued)
- Pressure with a Variable Frequency Drive (VFD) - T775U
- Carbon Dioxide (CO2) Sensing - T775U
- T775 APPLICATION REPLACEMENT EXAMPLES
- T775M2030 Replacement for W973A Logic Panel
- T775M2030 Replacement for W973A Logic Panel (continued)
- T775M2030 Replacement for W973A Logic Panel (continued)
- T775R Replacement for W964F Aquatrol Panel with Floating Actuator
- T775R Replacement for W964F Aquatrol Panel with Floating Actuator (continued)
- T775R Replacement for W964F Aquatrol Panel with Floating Actuator (continued)
- T775L Replacement for S984 Step Controller
- T775L Replacement for S984 Step Controller (continued)
- T775L Replacement for W7100C Discharge Air Controller
- T775L Replacement for W7100C Discharge Air Controller (continued)
- T775L Replacement for W7100C Discharge Air Controller (continued)
- T775 CROSS REFERENCE
- NOTES
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
17 63-7147—3
Chilled Water Reset (continued)
Device Checkout
The T775 performance can be checked out to determine if
proper operation exists.
For example, when the outside air temperature is at 80° F
(27° C), the chiller water temperature should be 52.5° F
(11° C). See Fig. 17. Use the alternate Home screens to
check that the effective setpoint is adjusting correctly based
on the outside air temperature (sensor B).
NOTE: The alternate Home screens do not show live
updates of the sensor temperature. They show the
temperature only at the moment the button is
pressed.
1. From the Home screen, use the $ button to verify
the setpoint temperature for each output.
2. Then, press the HOME button to view the actual
outside air temperature (sensor B).
Fig. 17. Chiller Setpoint vs. Outside Temperature.
M24876
CHILLED WATER
SETPOINT TEMPERATURE
OUTSIDE AIR
TEMPERATURE
60°
45°
48.75°
52.5°
56.25°
70°
90°
85°
80°
75°