62-0265—1 J.Z. 09-07
INSTALLATION
The 50021579-001 and T775-SENS-WR/WT remote probe
temperature sensors are single point temperature sensors with
Stainless Steel (304 Series) probes. Use care when installing
the probes. Pay attention not to kink the cable, especially on
the 5 ft units. The red/black wires should be securely
connected to the controller. The probe must be strapped tightly
to the pipe, duct, or device that is being monitored. A loose
attachment could affect the accuracy. To ensure good contact,
thermal grease is recommended. Insulating the sensor will
help the overall accuracy. When installing the T775-SENS-WR
sensor (5 ft cable), it may be necessary to wire tie the cable,
depending upon the application.
TROUBLESHOOTING
WEEE Directive
At the end of their useful life the packaging
and product should be disposed of via a
suitable recycle centre. Do not dispose of
with household waste. Do not burn.
If... Then...
Sensor reads 0 ohms or very low Sensor or wires are shorted together
Verify that (2) leads are not shorted to the probe.
Sensor reads infinity or very high Sensor or wires are cut or open
Erratic readings Bad wire connections - Condensation or Moisture problem
Inaccurate Sensor If you suspect that the sensor is not reading within the specified tolerance, disconnect the
sensor wires from the Building Management System (DDC Controller) and attach a NIST
traceable ohmmeter across the two wires. Compare the reading to the table listed below.
If you feel that the sensor is different from the table below please contact ACI for further
assistance.