User Guide

10 63-2604
Programming Temperature Setpoints
1. Press Occupied Heat.
2. Press upor down until the
desired temperature is displayed.
3. Press Occupied Cool.
4. Press upor down until the
desired temperature is displayed.
5. Press Not Occupied Heat.
6. Press upor down until the
desired temperature is displayed.
7. Press Not Occupied Cool.
8. Press upor down until the
desired temperature is displayed.
9. Press Run Schedule.
Temperature Setpoint Overrides
IMPORTANT
Setup determines Occupied override
duration.
Default duration is three hours.
NOTE: To cancel Override and immediately
return to the program, press Run
Schedule.
T7770 Setpoint Knob
A T7770 setpoint knob can remotely adjust the
T7350 setpoint. This adjustment can be made
when the sensor is in override.
NOTES:
During override, only occupied and
standby heat setpoints, and cool
setpoints are adjusted.
The maximum adjustment is ±5°F.