Submittal Sheet

All models except T6051B—
120 Vac 240 Vac
AC AC
T4051A,B,D
a
T6051A (heat) Full Load 16.0 8.0
T6052A (N.C. contacts)
T6052B (auto changeover Locked Rotor 96.0 48.0
heat and cool
T6051A (cool) Full Load 8.0 4.0
T6052A (N.O. contacts) Locked Rotor 48.0 24.0
120 Vac 240 Vac
AC AC
Heating Full Load 10.2 6.5
Locked Rotor 61.2 39.0
Cooling Full Load 7.4 4.0
Locked Rotor 44.4 24.0
a
T4051D also has resistive rating—22 amp at 120/240 Vac; 19
amp at 277 Vac.
Pilot Duty Rating (all models)—125 VA.
DIFFERENTIAL:
T4051, T6051—1 F [0.6 C].
T6052A—
–stage 1 heat, stage 2 cool—2.5 F [1.4 C] (nominal).
–stage 2 heat, stage 1 cool—3.2 F [1.8 C] (nominal).
T6052B—
–stage 1 heat—2.5 F [1.4 C] (nominal).
–stage 2 heat—3.2 F [1.8 C] (nominal).
SWITCHING:Snap-acting switch makes on temperature fall for
heating and on temperature rise for cooling. On T6052A, two
switches make in sequence for two-stage heating or cooling. On
T6052B, two switches make in sequence for auto changeover.
SCALE RANGE:
Fahrenheit—46 to 84 F; scale marked 50, 60, 70, 80.
Celsius—8 to 29 C; scale marked 10, 15, 20, 25.
MOUNTING: All models except T6051B mount directly on standard
outlet box. T6051B cast housing serves as outlet box.
COVER: Molded cover.
DIMENSIONS, IN INCHES [MILLIMETERS IN BRACKETS]: All
models except T6051B—5 [127] high, 3-1/8 [79.4] wide, 1-5/8
[41.3] deep. Switches and wiring terminals protrude into outlet
box 7/8 inch [22.2 mm]. T6051B—see Fig.1.
OPTIONAL SPECIFICATIONS:
1. T6051A with WARMER-COOLER scale; moisture fungus
treated.
2. T6051A, 46 to 84 Fahrenheit scale, for horizontal mounting.
3. T6051A with Celsius scale. Mounts either horizontally or
vertically.
4. T6052A with Celsius scale. Mounts either horizontally or
vertically.
5. T6052B with Celsius scale. Mounts either horizontally or
vertically.
6. T4051, T6051A, or T6052 with metal cover.
7. T4051, T6051A, or T6052 without thermometer.
Fig. 1—DIMENSIONS IN INCHES [mm IN BRACKETS]
PRINTED IN U.S.A.
T6051B Only—