Instruction Manual

Canadian DN-60437:C • 07/26/2010 — Page 3 of 4
End-of-Line Resistor: 4.7K ohm, 1/2 watt (P/N 71252 UL-
listed).
Standby Current: 2 mA.
Refer to the
Notifier Device Compatibility Document for listed
compatible devices.
Notification Appliance Circuits – TB5 (and TB 7 on SFP-
10UDC only):
Four NACs
Operation: Style Y (Class B)
Special Application power
Supervised and power-limited circuitry
Normal Operating Voltage: Nominal 24 VDC
Maximum Signaling Current: 7.0 A for SFP-5UDC, 2.5 A
maximum per NAC; 7.0 A for SFP-10UDC, 3.0 A maximum
per NAC.
End-of-Line Resistor: 4.7K ohm, 1/2 watt (Part #71252)
Max. Wiring Voltage Drop: 2 VDC
Refer to the
Notifier Device Compatibility Document for com-
patible listed devices.
Form C Relays – TB8:
Relay 1 (factory default programmed as Alarm Relay)
Relay 2 (factory default programmed as fail-safe Trouble
Relay)
Relay 3 (factory default programmed as Supervisory Relay)
Special Application Resettable Power – TB9:
Jumper selectable by JP31 for resettable or nonresettable
power.
Operating voltage: 24 VDC nominal.
Maximum available current: 500 mA - appropriate for pow-
ering four-wire smoke detectors.
Power-limited circuit.
Refer to the
Notifier Device Compatibility Document for listed
compatible devices.
Remote Sync Output - TB2: Remote power supply synchro-
nization output, only required for the SFP-5UDC. 24 VDC
nominal special application power. Maximum current is 40 mA.
End-of-Line Resistor: 4.7K ohm. Supervised and power-lim-
ited circuit.
Product Line Information
SFP-5UDC: Five-zone, 24-volt Fire Alarm Control Panel
(includes black backbox, FLPS-7 power supply, technical man-
ual, and a frame & post operating instruction sheet).
SFP-10UDC: Ten-zone, 24-volt Fire Alarm Control Panel
(includes black backbox, FLPS-7 power supply, technical man-
ual, and a frame & post operating instruction sheet).
OPTIONAL MODULES
N-CAC-5X: Optional (Class A) Converter Module. Converts
Style B (Class B) Initiating Device Circuits to Style D (Class A);
and Style Y (Class B) Notification Appliance Circuits to Style Z
(Class A). Connects to J2 on the SFP-5UDC and SFP-10UDC
main circuit board.
NOTE: Two Class A Converter Modules are required for the ten-
zone panel.
4XTM: Transmitter module. Provides a supervised output for
local energy municipal box transmitter and alarm and trouble
reverse polarity. Includes a disable switch and disable trouble
LED. A module jumper option allows the reverse polarity circuit
to open with a system trouble condition if no alarm conditions
exists. Mounts to the main circuit board connectors J4 and J5.
COMPATIBLE ANNUNCIATORS
N-ANN-LED: Comes mounted in the dress panel and provides
three LEDs for each zone: Alarm, Trouble, and Supervisory. In
non-ULC applications, additional N-ANN-LED modules can be
used for remote LED annunciation. Black. (For white, order N-
ANN-LED-W. For red, order N-ANN-LED-R.)
N-ANN-RLY: Relay module. Mounts inside the cabinet. Pro-
vides ten Form C relays.
N-ANN-80: Remote LCD Annunciator for non-ULC applica-
tions. Mimics the information displayed on the FACP’s LCD.
Black. (For white, order: N-ANN-80-W.)
N-ANN-S/PG: Serial/parallel printer gateway for non-ULC
applications. Provides a connection for a serial or parallel
printer.
N-ANN-I/O: Driver module for non-ULC applications. Provides
connections to a user-supplied graphic annunciator.
ACCESSORIES
BB-26: Battery backbox, holds up to two 25 AH batteries.
NFS-LBB: Battery backbox, holds up to two 55 AH batteries.
Black.
TR-CE-B: Optional black trim-ring for semi-flush mounted
cabinets.
PRN-6: UL listed printer for use in non-ULC applications.
firealarmresources.com