Controls and Indicators
LED INDICATORS
FIRE ALARM (red)
SUPERVISORY (yellow)
TROUBLE (yellow)
AC POWER (green)
ALARM SILENCED (yellow)
CONTROL BUTTONS
ACKNOWLEDGE
ALARM SILENCE
SYSTEM RESET (lamp test)
DRILL
Terminal Blocks
AC Power – TB1:
SFP-5UDC (FLPS-7 Power Supply): 120 VAC, 50/60 HZ,
3.90 A.
SFP-10UDC (FLPS-7 Power Supply): 120 VAC, 50/60 Hz,
3.90 A.
Wire size: minimum 14 AWG (2.00 mm²) with 600 V insula-
tion. Supervised, nonpower-limited.
Battery (sealed lead acid only) – J12:
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC
@ 1.4 A. Supervised, nonpower-limited.
Maximum Charger Capacity: 18 AH battery for SFP-5UDC,
and 26 AH battery for SFP-10UDC. [Two 18 Ah batteries
can be housed in the FACP cabinet. Larger batteries
require separate battery box such as the BB-26 or NFS-
LBB.]
Minimum Battery Size: 12 AH.
Initiating Device Circuits – TB4 (and TB 6 on SFP-10UDC
only):
Alarm Zones 1 - 5 on TB 4 (SFP-5UDC and SFP-10UDC).
Alarm Zones 6 - 10 on TB6 (SFP-10UDC only).
Supervised and power-limited circuitry.
Operation: All zones Style B (Class B).
Normal Operating Voltage: Nominal 20 VDC.
Alarm Current: 15 mA minimum.
Short Circuit Current: 40 mA max.
Maximum Loop Resistance: 100 ohms.
Cabinet Measurements
52416cab.wmf