Instruction Manual
Page 2 of 4 — Canadian DN-60437:C • 07/26/2010
Controls and Indicators
LED INDICATORS
• FIRE ALARM (red)
• SUPERVISORY (yellow)
• TROUBLE (yellow)
• AC POWER (green)
• ALARM SILENCED (yellow)
CONTROL BUTTONS
• ACKNOWLEDGE
• ALARM SILENCE
• SYSTEM RESET (lamp test)
• DRILL
Terminal Blocks
AC Power – TB1:
• SFP-5UDC (FLPS-7 Power Supply): 120 VAC, 50/60 HZ,
3.90 A.
• SFP-10UDC (FLPS-7 Power Supply): 120 VAC, 50/60 Hz,
3.90 A.
• Wire size: minimum 14 AWG (2.00 mm²) with 600 V insula-
tion. Supervised, nonpower-limited.
Battery (sealed lead acid only) – J12:
• Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC
@ 1.4 A. Supervised, nonpower-limited.
• Maximum Charger Capacity: 18 AH battery for SFP-5UDC,
and 26 AH battery for SFP-10UDC. [Two 18 Ah batteries
can be housed in the FACP cabinet. Larger batteries
require separate battery box such as the BB-26 or NFS-
LBB.]
• Minimum Battery Size: 12 AH.
Initiating Device Circuits – TB4 (and TB 6 on SFP-10UDC
only):
• Alarm Zones 1 - 5 on TB 4 (SFP-5UDC and SFP-10UDC).
• Alarm Zones 6 - 10 on TB6 (SFP-10UDC only).
• Supervised and power-limited circuitry.
• Operation: All zones Style B (Class B).
• Normal Operating Voltage: Nominal 20 VDC.
• Alarm Current: 15 mA minimum.
• Short Circuit Current: 40 mA max.
• Maximum Loop Resistance: 100 ohms.