Instruction Manual
DN-60437:C • 07/26/2010 — Page 1 of 4
SFP-5UDC/SFP-10UDC
Five Zone Fire Alarm Control Panel
Ten Zone Fire Alarm Control Panel
Conventional Fire Alarm Control Panels
Canadian DN-60437:C
60437cov.jpg
SFP-5UDC
General
The SFP-5UDC is a five-zone FACP (Fire Alarm Control
Panel) and the SFP-10UDC is a ten-zone FACP. These control
panels provide reliable fire signaling protection for small to
medium-sized commercial, industrial, and institutional build-
ings. Both panels include built-in communicators for Central
Station Service and remote upload/download.
Each of these FACPs is compatible with System Sensor’s
microprocessor-based i
3
series detectors. These conventional
smoke detectors can transmit a maintenance trouble signal to
the FACP indicating the need for cleaning and a supervisory
“freeze” signal when the ambient temperature falls below the
detector rating. Additionally, both the SFP-5UDC and SFP-
10UDC are compatible with conventional input devices such
as two- and four-wire smoke detectors, pull stations, waterflow
devices, tamper switches, and other normally-open contact
devices. Refer to the
Notifier Device Compatibility Document
for a complete listing of compatible devices.
Outputs include four NACs (Notification Appliance Circuits),
three programmable Form-C relays (factory programmed for
Alarm, Trouble, and Supervisory) and 24 VDC special applica-
tion resettable and nonresettable power outputs. The FACPs
supervise all wiring, AC voltage, battery level and telephone
line integrity.
Activation of a compatible smoke detector or any normally-
open fire alarm initiating device will activate audible and visual
signaling devices, illuminate an indicating LED, sound the
piezo sounder at the FACP, activate the communicator and
FACP alarm relay, and operate an optional module used to
notify a remote station or initiate an auxiliary control function.
Features
• Listed to ULC S527-99, S559-01.
Listed to UL Standard 864, 9th edition.
• Built-in DACT (Digital Alarm Communicator/Transmitter).
• Style B (Class B) IDC (Initiating Device Circuit)
– SFP-5UDC - five IDCs.
– SFP-10UDC - ten IDCs.
• Style Y (Class B) NAC (Notification Appliance Circuit) - spe-
cial application power
– SFP-5UDC - four NACs.
– SFP-10UDC - four NACs.
• Notification Appliances may be programmed as
– Silence Inhibit.
– Auto-Silence.
– Strobe Synchronization for System Sensor, Wheelock,
Gentex, Faraday, or Amseco devices.
– Selective Silence (horn-strobe mute).
– Temporal or Steady Signal.
– Silenceable or Nonsilenceable.
• Optional N-CAC-5X Style Z (Class A) Converter Module for
NACs and IDCs (2 required for SFP-10UDC).
• Form-C Relays for Alarm, Trouble and Supervisory - Con-
tact Ratings 2.0 A@ 30 VDC or 0.5 A @ 30 VAC (resistive).
• 7.0 A total system current for SFP-5UDC.
• 7.0 A total system current for SFP-10UDC.
• Optional Trim Ring TR-CE-B for semi-flush mounting.
• 24 volt operation.
• Low AC voltage sense.
• Alarm Verification.
• PAS (Positive Alarm Sequence).
• Automatic battery trickle charger.
• Built-in LED Annunciator Module N-ANN-LED
• Optional 4XTM module (conventional reverse polarity/city
box transmitter).
PROGRAMMING AND SOFTWARE:
• Can be programmed at the panel with no special software
or additional equipment.
• Programmable Make/Break Ratio.
• Upload/Download (local or remote) of program and data via
integral DACT.
USER INTERFACE:
• Built-in DACT (Digital Alarm Communicator/Transmitter).
• Integral 80-character LCD display with backlighting and
keypad.
• Real-time clock/calendar with automatic daylight savings
adjustments.
• ANN-BUS for connection to annunciators.
• Audible or silent walk test capabilities.
• Piezo sounder for alarm, trouble, and supervisory.