System Capacity
• Annunciators ...................................................................... 8
Electrical Specifications
• SFP-5UD(R) (FLPS-3 Power Supply): 120 VAC, 60 HZ,
1.0 A
• SFP-10UD(R) (FLPS-7 Power Supply): 120 VAC, 60 HZ,
3.90 A
• SFP-5UDE (FLPS-3 Power Supply): 240 VAC, 50 HZ,
0.54 A.
• SFP-10UDE (FLPS-7 Power Supply): 240 VAC, 50 HZ,
2.20 A.
•
Wire size:
minimum 14 AWG (2.0 mm
2
) with 600 V insula-
tion, supervised, nonpower-limited
Cabinet Specifications
Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x
0.72" (1.82 cm.) deep. Backbox: 19.00" (48.26 cm.) high x
16.65" (42.29 cm.) wide x 5.25" (13.34 cm.) deep. Trim Ring
(TR-CE): 22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide.
Shipping Specifications
Dimensions:
– 20.00" (50.80 cm.) high
– 22.5" (57.15 cm.) wide
– 8.5" (21.59 cm.) deep.
Weight: 27 lb (12.20 kg)
Temperature and Humidity Ranges
This system meets NFPA requirements for operation at 0 –
49°C/32 – 120°F and at a relative humidity 93% ± 2% RH
(noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the
useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme tempera-
ture ranges and humidity. Therefore, it is recommended that
this system and its peripherals be installed in an environment
with a normal room temperature of 15 – 27°C/60 – 80°F.
Agency Listings and Approvals
The listings and approvals below apply to the basic SFP-5UD
and SFP-10UD control panels. In some cases, certain mod-
ules or applications may not be listed by certain approval
agencies, or listing may be in process. Consult factory for lat-
est listing status.
• UL Listed: File S635
• FM Approved
• CSFM: 7165-0028:246
• MEA: MEA: 333-07-E
NOTE: For ULC-listed models, see dn-60437.
NFPA Standards
The SFP-5UD/SFP-10UD(E) complies with the following NFPA
72 Fire Alarm Systems requirements:
– LOCAL (Automatic, Manual, Waterflow and Sprinkler
Supervisory).
–AUXILIARY (Automatic, Manual and Waterflow) (requires
4XTM).
– REMOTE STATION (Automatic, Manual and Waterflow)
(Where a DACT is not accepted, the alarm, trouble and
supervisory relays may be connected to UL 864 listed
transmitters. For reverse polarity signaling of alarm and
trouble, 4XTM is required.)
–PROPRIETARY (Automatic, Manual and Waterflow).
– CENTRAL STATION (Automatic, Manual and Waterflow,
and Sprinkler Supervised).
–OT, PSDN (Other Technologies, Packet-switched Data
Network)
NOTIFIER® and System Sensor® are registered trademarks of Honeywell
International Inc.
©2009 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
Made in the U.S. A.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
SYSTEM SPECIFICATIONS
firealarmresources.com