USER INTERFACE:
Built-in DACT (Digital Alarm Communicator/Transmitter).
Integral 80-character LCD display with backlighting and
keypad.
Real-time clock/calendar with automatic daylight savings
adjustments.
ANN-BUS for connection to remote annunciators.
Audible or silent walk test capabilities.
Piezo sounder for alarm, trouble, and supervisory.
Controls and Indicators
LED INDICATORS
FIRE ALARM (red)
SUPERVISORY (yellow)
TROUBLE (yellow)
AC POWER (green)
ALARM SILENCED (yellow)
CONTROL BUTTONS
ACKNOWLEDGE
ALARM SILENCE
SYSTEM RESET (lamp test)
•DRILL
Terminal Blocks
AC Power – TB1:
SFP-5UD (FLPS-3 Power Supply): 120 VAC, 50/60 HZ,
1.00 A.
SFP-10UD (FLPS-7 Power Supply): 120 VAC, 50/60 Hz,
3.8 A.
SFP-10UDE (FLPS-7 Power Supply): 240 VAC, 50 HZ,
2.20 A.
Wire size: minimum 14 AWG (2.00 mm²) with 600 V insulation.
Supervised, nonpower-limited.
Battery (sealed lead acid only) – J12:
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC
@ 1.4 A. Supervised, nonpower-limited.
Maximum Charger Capacity: 18 AH battery for SFP-5UD,
and 26 AH battery for SFP-10UD(E). [Two 18 Ah batteries
can be housed in the FACP cabinet. Larger batteries
require separate battery box such as the BB-26 or NFS-
LBB.]
Minimum Battery Size: 7 AH.
Cabinet Measurements
52416cab.wmf