USER INTERFACE:
• Built-in DACT (Digital Alarm Communicator/Transmitter).
• Integral 80-character LCD display with backlighting and
keypad.
• Real-time clock/calendar with automatic daylight savings
adjustments.
• ANN-BUS for connection to remote annunciators.
• Audible or silent walk test capabilities.
• Piezo sounder for alarm, trouble, and supervisory.
Controls and Indicators
LED INDICATORS
• FIRE ALARM (red)
• SUPERVISORY (yellow)
• TROUBLE (yellow)
• AC POWER (green)
• ALARM SILENCED (yellow)
CONTROL BUTTONS
• ACKNOWLEDGE
• ALARM SILENCE
• SYSTEM RESET (lamp test)
•DRILL
Terminal Blocks
AC Power – TB1:
•
SFP-5UD (FLPS-3 Power Supply): 120 VAC, 50/60 HZ,
1.00 A.
• SFP-10UD (FLPS-7 Power Supply): 120 VAC, 50/60 Hz,
3.8 A.
• SFP-10UDE (FLPS-7 Power Supply): 240 VAC, 50 HZ,
2.20 A.
Wire size: minimum 14 AWG (2.00 mm²) with 600 V insulation.
Supervised, nonpower-limited.
Battery (sealed lead acid only) – J12:
• Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC
@ 1.4 A. Supervised, nonpower-limited.
• Maximum Charger Capacity: 18 AH battery for SFP-5UD,
and 26 AH battery for SFP-10UD(E). [Two 18 Ah batteries
can be housed in the FACP cabinet. Larger batteries
require separate battery box such as the BB-26 or NFS-
LBB.]
• Minimum Battery Size: 7 AH.
Cabinet Measurements
52416cab.wmf