Submittal Sheet

7800 SERIES S7800A2142 KEYBOARD DISPLAY MODULE
32-00110—05 48
Fig. 75. Commission RESET button
After the RESET button has been held for 5 seconds the burner control module indicates that commissioning is
successfully done (see Fig. 76). The left arrow or OK button can be pressed to exit commissioning and go back to the
commissioning menu.
Fig. 76. Commissioning successfully completed
Each step of the commissioning procedure must be performed within 30 seconds after the page is displayed for the step.
If the RESET button is released too early (less than 5 seconds) or the user doesn’t respond to a procedure step within 30
seconds, the commissioning session is terminated by the burner control module and this failure is indicated on the page
(see Fig. 77 for an example).
Fig. 77. Failed commissioning step
The user has the option to restart commissioning or not if the session fails to end completely. The “Yes” option is selected
and the OK button pressed to redo commissioning by logging in again (see Fig. 67). The “No” option is selected and the
OK button pressed to not redo commissioning which exits this page and returns back to the commissioning menu to
show the current settings (see Fig. 64). The right and left arrow buttons are used to tab between the “Yes” and “No”
options.