Submittal Sheet

7800 SERIES S7800A2142 KEYBOARD DISPLAY MODULE
47 32-00110—05
Fig. 72. Confirm valve proving when option
The right and left arrow buttons are used to tab between the “Yes” and “No” commands. When the decision is made the OK
button is pressed to inform the burner control module. A “No” command stops the commissioning and control returns
back to the commissioning menu. A “Yes” command causes the setting to be approved and one of the following pages to
automatically display next (directed by the burner control module):
Valve Proving (VP) time confirmation (VP when setting is not disabled) – see next figure
Postpurge time confirmation (VP when setting is disabled and postpurge time has been configured) – see Fig. 74
Burner commission reset (VP when setting is disabled and postpurge time was not configured) – see Fig. 75
The user is asked to confirm the valve proving time setting in the following page (see next figure). The time setting is
displayed on the page, and the user confirms it with a “Yes” answer or declines it with a “No” answer.
Fig. 73. Confirm valve proving time
The right and left arrow buttons are used to tab between the “Yes” and “No” commands. When the decision is made the OK
button is pressed to inform the burner control module. A “No” command stops the commissioning and control returns
back to the commissioning menu. A “Yes” command causes the setting to be approved and one of the following pages to
automatically display next (directed by the burner control module):
Postpurge time confirmation (postpurge time was configured earlier) – see next figure
Burner commission reset (postpurge time was not configured earlier) – see Fig. 75
The user is asked to confirm the postpurge time setting in the following page (see next figure). The time setting is
displayed on the page, and the user confirms it with a “Yes” answer or declines it with a “No” answer.
Fig. 74. Confirm postpurge time
The right and left arrow buttons are used to tab between the “Yes” and “No” commands. When the decision is made the OK
button is pressed to inform the burner control module. A “No” command stops the commissioning and control returns
back to the commissioning menu. A “Yes” command causes the setting to be approved and the Burner commission reset
page (see next figure) to automatically be displayed (directed by the burner control module).
The Burner commission reset page is displayed for the final step of the commissioning procedure. After all configuration
and confirmations are done the RESET button on the burner control module must be pressed and held for 5 seconds. This
page (see Fig. 75) automatically displays when the burner control module wants this reset action to be performed.
SETTING
ENTERED
EARLIER
SETTING
ENTERED
EARLIER
SETTING
ENTERED
EARLIER