Submittal Sheet
Table Of Contents
7800 SERIES S7800A2142 KEYBOARD DISPLAY MODULE
32-00110—05 44
Fig. 65. Enter commissioning
If the burner control is not in a state that permits commissioning to proceed, the commissioning setup menu displays this
fact, but does display the current parameter settings (see Fig. 66). Only action permitted in this case is to press the left
arrow button to exit the menu and return back to the Display setup menu page.
Fig. 66. Commissioning not permitted
When commissioning is allowed the user has the option to continue on with commissioning by selecting the “Yes”
command or to exit the menu and not do commissioning with the “No” command. The right and left arrow buttons tab
between the two options. Pressing the OK button executes the highlighted command. If “No” is selected, control returns
back to the page that it originated from (Home or Display Menu). If “Yes” is selected, the user is requested to log into the
burner control module with the commissioning password (see Fig. 67).
Fig. 67. Commissioning login
The commissioning password is “78”. The password is entered by scrolling the digits to “78” using the up and down arrow
buttons when in the digit positions. The right and left arrow buttons navigate between the digits and the “Yes” and “No”
commands. When the input focus is on the “Yes” and “No” commands the up and down arrow buttons tab between these
two options. Pressing the OK button when the input focus is on “Yes” or “No” executes the command. A “Yes” command
sends the password to the burner control module to begin commissioning. A successful login transitions to the first
commission page. An unsuccessful login (wrong password) displays an “INVALID PASSWORD” message (see Fig. 68). If
the “No” command is selected, commissioning is canceled and control returns to the previous page.
COMMISSIONING CAN’T
BE DONE AT THIS TIME